Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 6, 2021, 06:31 AM
  • 16 0356_16 0355_10052021_234430.mp4

Date
10/05/2021
W/O
916512
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00665
PipeID
P13407
Time
11:31 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9434
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
SAN MARINO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_916512_TV16060_OCT2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Width
16 in.
Upstream MH
16 0356
Downstream MH
16 0355
Dir. of Survey
Downstream
Length Surveyed
281.4 ft.
Total Length
281.4 ft.
Structural Index
4
Structural Quick
4J00
Structural Rating
220
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
220
Pipe schematic from manhole 16 0356 to 16 0355
MH: 16 0356MH: 16 0355downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 6 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - 16 03560 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area5.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start43.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"45.5 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"144.9 ft. TS - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6" - protruding, 1/4"245.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"247.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"280 ft. MGO - General Observation - Surface Spalling throughout the reach, 9 to 3 oclock281.4 ft. AMH - Downstream Manhole, Survey Ends - 16 0355281.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

    45.5 ft. - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6" - protruding, 1/4"

    144.9 ft. - Tap Saddle, at 02 o'clock, -, within 8 inches of joint: NO, 6" - protruding, 1/4"

Observations (13)

DistanceCodeObservation
281.4AMH16 0355
245.2TFC
0MGOCONNECTION AT THE MH 6 OC'LOCK
0AMH16 0356
45.5TB
43.6TF
280MGOSurface Spalling throughout the reach, 9 to 3 oclock
0MWL
0MWM
5.6FM
144.9TSprotruding, 1/4"
247.3TF
281.4FM

Properties (7)

additional_info
630074100521201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-10-05T23:31:43-07:00
documentation
PROPIPE
is_lateral_inspection
false