Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 6, 2021, 07:39 AM
  • 16 0336_16 0335_10062021_004939.mp4

Date
10/06/2021
W/O
916512
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00665
PipeID
P13387
Time
12:39 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9434
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
SAN MARINO
Loc. details
Sidewalk
Location Code
F
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_916512_TV16060_OCT2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Width
16 in.
Upstream MH
16 0336
Downstream MH
16 0335
Dir. of Survey
Downstream
Length Surveyed
202.2 ft.
Total Length
202.2 ft.
Structural Index
4
Structural Quick
4G00
Structural Rating
156
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
156
Pipe schematic from manhole 16 0336 to 16 0335
MH: 16 0336MH: 16 0335downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 03360 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK8.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start33.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"36.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"105 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"107.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"179.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"182.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"200 ft. MGO - General Observation - Surface Spalling throughout, 9 to 3 oclock202.2 ft. AMH - Downstream Manhole, Survey Ends - 16 0335202.2 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK202.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
182.2TFC
107.7TFC
0MWM
179.7TFC
200MGOSurface Spalling throughout, 9 to 3 oclock
202.2AMH16 0335
202.2MGOCONNECTION AT THE MH 9 OC'LOCK
105TF
8.2FM
202.2FM
0AMH16 0336
33.6TF
0MWL
0MGOCONNECTION AT THE MH 9 OC'LOCK
36.2TFC

Properties (7)

additional_info
630074100521201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-10-06T00:39:31-07:00
documentation
PROPIPE
is_lateral_inspection
false