Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 6, 2021, 08:00 AM
  • 16 0334_16 0333_10062021_011012.mp4

Date
10/06/2021
W/O
916512
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00665
PipeID
P13385
Time
1:00 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9434
Sewer Name
16 SAN MARINO OUTFALL TRUNK
City
SAN MARINO
Loc. details
Easement/Right of Way
Location Code
D
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
20
Purpose
Routine Assessment
Project
RFIR_WO_916512_TV16060_OCT2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
20 in.
Width
20 in.
Upstream MH
16 0334
Downstream MH
16 0333
Dir. of Survey
Downstream
Length Surveyed
220.4 ft.
Total Length
220.4 ft.
Structural Index
3
Structural Quick
3F00
Structural Rating
108
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
108
Pipe schematic from manhole 16 0334 to 16 0333
MH: 16 0334MH: 16 0333downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 03340 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 30 %of cross sectional area5.8 ft. MMC - Material Change, Cast Iron5.8 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start102.9 ft. SCP - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish115.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES140.2 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start151.2 ft. TB - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"219 ft. MGO - General Observation - Surface Spalling throughout, 9 to 3 oclock220.4 ft. AMH - Downstream Manhole, Survey Ends - 16 0333220.4 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Finish

Observation photos (5)

  • Material Change, Cast Iron

    5.8 ft. - Material Change, Cast Iron

  • Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.8 ft. - Surface Corrosion Metal Pipe, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    115.7 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

    140.2 ft. - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

    151.2 ft. - Tap Break-In, at 01 o'clock, -, within 8 inches of joint: NO, 6"

Observations (12)

DistanceCodeObservation
5.8MMC
5.8SCP
219MGOSurface Spalling throughout, 9 to 3 oclock
102.9SCP
140.2FL
151.2TB
0AMH16 0334
220.4AMH16 0333
220.4FL
0MWL
115.7CM
0MWM

Properties (7)

additional_info
630074100521201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-10-06T01:00:04-07:00
documentation
PROPIPE
is_lateral_inspection
false