Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 5, 2021, 05:38 AM
  • 16 0107_16 0106_10042021_225314.mp4

Date
10/04/2021
W/O
916620
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00641
PipeID
P13145
Time
10:38 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9147
Sewer Name
16 ALLEN AVENUE TRUNK, SECTION 5
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
14
Purpose
Routine Assessment
Project
RFIR_WO_916620_TV16009_OCT2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
16 0107
Downstream MH
16 0106
Dir. of Survey
Downstream
Length Surveyed
379.8 ft.
Total Length
379.8 ft.
Structural Index
3
Structural Quick
3N2N
Structural Rating
375
O&M Index
2
O&M Quick
2N00
O&M Rating
150
Overall Index
2
Overall Quick
Overall Rating
525
Pipe schematic from manhole 16 0107 to 16 0106
MH: 16 0107MH: 16 0106downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 01072 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. MGO - General Observation - 25% MAG COAT212.1 ft. TFA - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 4", 4"377 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish377 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish378.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish379.8 ft. AMH - Downstream Manhole, Survey Ends - 16 0106

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - 25% MAG COAT

    2 ft. - General Observation - 25% MAG COAT

  • Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 4", 4"

    212.1 ft. - Tap Factory Made Active, at 11 o'clock, -, within 8 inches of joint: YES, 4", 4"

Observations (12)

DistanceCodeObservation
0MWM
377DAGS
377SSS
0MWL
0AMH16 0107
212.1TFA
2SAV
378.9SAV
2DAGS
379.8AMH16 0106
2SSS
2MGO25% MAG COAT

Properties (7)

additional_info
630074100421201
custom_field_three
AGGREGATE VISIBLE
custom_field_two
3
customer
1
datetime
2021-10-04T22:38:08-07:00
documentation
PRO PIPE
is_lateral_inspection
false