Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 5, 2021, 08:09 AM
  • 16 0100_16 0099_10052021_012343.mp4

Date
10/05/2021
W/O
916620
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00641
PipeID
P13138
Time
1:09 AM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9147
Sewer Name
16 ALLEN AVENUE TRUNK, SECTION 5
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
14
Purpose
Routine Assessment
Project
RFIR_WO_916620_TV16009_OCT2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
16 0100
Downstream MH
16 0099
Dir. of Survey
Downstream
Length Surveyed
376.8 ft.
Total Length
376.8 ft.
Structural Index
3
Structural Quick
3N2N
Structural Rating
375
O&M Index
2
O&M Quick
2N00
O&M Rating
148
Overall Index
2
Overall Quick
Overall Rating
523
Pipe schematic from manhole 16 0100 to 16 0099
MH: 16 0100MH: 16 0099downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 16 01000 ft. MWL - Water Level, 15 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.6 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.6 ft. MGO - General Observation - 60% MAG COAT374 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish375.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish375.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish376.8 ft. AMH - Downstream Manhole, Survey Ends - 16 0099

Observation photos (3)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.6 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - 60% MAG COAT

    2.6 ft. - General Observation - 60% MAG COAT

Observations (11)

DistanceCodeObservation
2.6SSS
0MWM
374DAGS
0AMH16 0100
2DAGS
375.9SSS
375.9SAV
2.6SAV
0MWL
2.6MGO60% MAG COAT
376.8AMH16 0099

Properties (7)

additional_info
630074100421201
custom_field_three
AGGREGATE VISIBLE/SPALLING
custom_field_two
3
customer
1
datetime
2021-10-05T01:09:39-07:00
documentation
PRO PIPE
is_lateral_inspection
false