Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 2, 2021, 08:57 AM
  • 22 0742_22 0741_1222021_011445.mp4

Date
12/02/2021
W/O
0921912
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00821
PipeID
P17098
Time
12:57 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H2032
Sewer Name
22 PUDDINGSTONE TRUNK, SECTS 1&2
City
SAN DIMAS
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
23
Purpose
Capital Improvement Program Assesment
Project
20211202MDM_PUDDINGSTONE_TRUNK_SECTS_1_2
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0742
Downstream MH
22 0741
Dir. of Survey
Downstream
Length Surveyed
275 ft.
Total Length
275 ft.
Structural Index
3
Structural Quick
4224
Structural Rating
16
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
20
Pipe schematic from manhole 22 0742 to 22 0741
MH: 22 0742MH: 22 0741downstream0 ft. AMH - Upstream Manhole, Survey Begins - 1:00AM0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 40 %of cross sectional area2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE SEVERE AGG ATTACHED2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG8.8 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED33.2 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG38.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped87.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped91.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open94.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVEWRE AGG ATTACHED137.4 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - PEELING CONCRETE SEVERE AGG ATTACHED140.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped144.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped185.1 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped 100% GREASE189.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped238.2 ft. TFD - Tap Factory Made Defective, at 11 o'clock, -, within 8 inches of joint: YES, 6" - Open-100% GREASE242.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open246.3 ft. TB - Tap Break-In, at 09 o'clock, -, within 8 inches of joint: YES, 6" - Open273.5 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active273.5 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - PEELING CONCRETE SEVERE AGG ATTACHED273.5 ft. SAM - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish - SEVERE AGG275 ft. AMH - Downstream Manhole, Survey Ends - 1:50AM

Observation photos (6)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE SEVERE AGG ATTACHED

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

    2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: YES, Start - SEVERE AGG

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

    8.8 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVERE AGG ATTACHED

  • Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

    33.2 ft. - Surface Aggregate Missing, from 09 to 03 o'clock, within 8 inches of joint: NO - SEVERE AGG

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVEWRE AGG ATTACHED

    94.4 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: NO - PEELING CONCRETE SEVEWRE AGG ATTACHED

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - PEELING CONCRETE SEVERE AGG ATTACHED

    137.4 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES - PEELING CONCRETE SEVERE AGG ATTACHED

Observations (23)

DistanceCodeObservation
275AMH1:50AM
185.1TFDCapped 100% GREASE
273.5MGOConn. @ Mh, 3 O' Clock. Active
91.8TFOpen
0AMH1:00AM
2SSSBLISTERING PEELING CONCRETE SEVERE AGG ATTACHED
87.7TFCapped
2SAMSEVERE AGG
246.3TBOpen
242.4TFCOpen
238.2TFDOpen-100% GREASE
94.4SSSPEELING CONCRETE SEVEWRE AGG ATTACHED
0MWL
0MWM
273.5SSSPEELING CONCRETE SEVERE AGG ATTACHED
38.7TFCapped
189.9TFCCapped
140.6TFCCapped
273.5SAMSEVERE AGG
33.2SAMSEVERE AGG
137.4SSSPEELING CONCRETE SEVERE AGG ATTACHED
8.8SSSPEELING CONCRETE SEVERE AGG ATTACHED
144.9TFCCapped

Properties (6)

custom_field_three
PEELING CONCRETE LAYERS SEVERE AGG ATTACHED
custom_field_two
1
customer
LACSD
datetime
2021-12-02T00:57:36-08:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false