- Date
- 12/01/2021
- W/O
- 0922094
- Weather
- Dry
- Operator/Surveyor
- MARTIN
- Sewer ID
- Z00091
- PipeID
- P08911
- Time
- 1:43 AM
- Certificate
- U-1014-06022543
- System Owner
- LACSD
- Date Cleaned
- —
- Pre-Cleaning
- Not Known
- Media Label
- H2030
- Sewer Name
- B JOINT OUTFALL B - UNIT 5A
- City
- SAM MARIO
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 15
- Page No.
- 07
- Purpose
- Capital Improvement Program Assesment
- Project
- 20211201MDM_JOINT_OUTFALL_B_UNIT_5A
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 24 in.
- Upstream MH
- B 0399
- Downstream MH
- B 0398
- Dir. of Survey
- Downstream
- Length Surveyed
- 357.8 ft.
- Total Length
- 357.8 ft.
- Structural Index
- 3
- Structural Quick
- 4133
- Structural Rating
- 15
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 15
Pipe schematic from manhole B 0399 to B 0398 Observation photos (5)

2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start - BLISTERING PEELING CONCRETE

2 ft. - General Observation - 90% MAG COAT START

4.8 ft. - Surface Aggregate Visible, from 10 to 02 o'clock, within 8 inches of joint: NO - SEVERE AGG

111.8 ft. - Surface Aggregate Visible, from 01 to 03 o'clock, within 8 inches of joint: YES - SEVERE AGG

191.7 ft. - Surface Aggregate Projecting, from 01 to 05 o'clock, within 8 inches of joint: YES - SEVERE AGG