Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 3, 2021, 06:25 PM
  • 02 2089_02 1898_1232021_105821.mp4

  • 02 2089_02 1898_1232021_113028.mp4

Date
12/03/2021
W/O
0886314
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00247
PipeID
P04405
Time
10:25 AM
Certificate
U-1014-06022541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H2036
Sewer Name
02 DOUGLAS AVENUE RELIEF TRUNK
City
EAST LOS ANGELES
Loc. details
Other
Location Code
Z
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
08
Purpose
Capital Improvement Program Assesment
Project
20211203SHO_DOUGLAS_AVENUE_RELIEF_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
02 2089
Downstream MH
02 1898
Dir. of Survey
Downstream
Length Surveyed
243.3 ft.
Total Length
243.3 ft.
Structural Index
3
Structural Quick
5141
Structural Rating
14
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
14
Pipe schematic from manhole 02 2089 to 02 1898
MH: 02 2089MH: 02 1898downstream0 ft. AMH - Upstream Manhole, Survey Begins - MH 20890 ft. MWM - Water Mark, 15 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area13.8 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 4"16.2 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 4"29.9 ft. SSS - Surface Spalling, at 04 o'clock, within 8 inches of joint: YES49.6 ft. JOM - Joint Offset Medium61.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"70.7 ft. B - Broken, from 10 to 12 o'clock, within 8 inches of joint: YES104.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 4"110 ft. MWLS - Water Level, Sag in pipe, 55 %of cross sectional area, Start136.5 ft. MWLS - Water Level, Sag in pipe, 55 %of cross sectional area, Finish142.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 4"205 ft. TF - Tap Factory Made, at 12 o'clock, -, within 8 inches of joint: YES, 4"240 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES243.3 ft. AMH - Downstream Manhole, Survey Ends - MH 1898

Observation photos (2)

  • Joint Offset Medium

    49.6 ft. - Joint Offset Medium

  • Broken, from 10 to 12 o'clock, within 8 inches of joint: YES

    70.7 ft. - Broken, from 10 to 12 o'clock, within 8 inches of joint: YES

Observations (16)

DistanceCodeObservation
0AMHMH 2089
16.2TF
243.3AMHMH 1898
13.8TFC
136.5MWLS
49.6JOM
104.6TF
142.6TF
70.7B
61.8TF
0MWM
29.9SSS
110MWLS
0MWL
205TF
240FC

Properties (6)

additional_info
RFIR
custom_field_two
2
customer
LACSD
datetime
2021-12-03T10:25:37-08:00
documentation
OBREGON, RUVALCABA, RAMIREZ
is_lateral_inspection
false