Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Dec 1, 2021, 06:12 PM
  • 22 0675_22 0674A_1212021_102715.mp4

Date
12/01/2021
W/O
0917236
Weather
Dry
Operator/Surveyor
SANTIAGO OBREGON
Sewer ID
Z00827
PipeID
P27148
Time
10:12 AM
Certificate
U-1014-06025541
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H2031
Sewer Name
22 SUNFLOWER TRUNK
City
SAN DIMAS
Loc. details
Main Highway - Suburban/Rural
Location Code
B
Use of Sewer
Sanitary Sewer
District
District 22
Page No.
15
Purpose
Routine Assessment
Project
20211201SHO_SUNFLOWER_TRUNK
Material
NRCP
Shape
Circular
Height
15 in.
Upstream MH
22 0675
Downstream MH
22 0674A
Dir. of Survey
Downstream
Length Surveyed
192.4 ft.
Total Length
192.4 ft.
Structural Index
3
Structural Quick
3121
Structural Rating
5
O&M Index
2
O&M Quick
2100
O&M Rating
2
Overall Index
2
Overall Quick
Overall Rating
7
Pipe schematic from manhole 22 0675 to 22 0674A
MH: 22 0675MH: 22 0674Adownstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - MH 6750 ft. MWM - Water Mark, 35 %of cross sectional area9.9 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start9.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start25.3 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: NO, 4" - DEBRIS30.4 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 4"105.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"110.8 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 4"176.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 4"181.5 ft. TFC - Tap Factory Made Capped, at 11 o'clock, -, within 8 inches of joint: NO, 4"190.7 ft. MGO - General Observation - LIGHT MAG COAT THROUGHOUT191.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish191.5 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish192.4 ft. AMH - Downstream Manhole, Survey Ends - MH 674A

Observation photos (2)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.9 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    9.9 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (15)

DistanceCodeObservation
191.5SSS
9.9SAV
191.5SAV
110.8TFC
192.4AMHMH 674A
9.9SSS
105.9TFC
0MWL
176.3TFC
25.3TFDDEBRIS
30.4TFC
181.5TFC
0AMHMH 675
190.7MGOLIGHT MAG COAT THROUGHOUT
0MWM

Properties (6)

custom_field_three
SPALLING + AGG.
custom_field_two
2
customer
LACSD
datetime
2021-12-01T10:12:27-08:00
documentation
OBREGON, IGNACIO, RUVALCABA, RAMIREZ
is_lateral_inspection
false