- Date
- 10/15/2021
- W/O
- 916413
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00165
- PipeID
- P10540
- Time
- 1:08 AM
- Certificate
- U-508-7069
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K9446
- Sewer Name
- H JOINT OUTFALL H - UNIT 1F
- City
- HUNTINGTON PARK
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 01
- Page No.
- 08
- Purpose
- Routine Assessment
- Project
- RFIR_WO_916413_TV01220_OCT2021
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 36 in.
- Width
- 36 in.
- Upstream MH
- H 0088
- Downstream MH
- H 0087
- Dir. of Survey
- Downstream
- Length Surveyed
- 660.8 ft.
- Total Length
- 660.8 ft.
- Structural Index
- 3
- Structural Quick
- 5Y3Y
- Structural Rating
- 1311
- O&M Index
- 0
- O&M Quick
- 0000
- O&M Rating
- 0
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 1311
Pipe schematic from manhole H 0088 to H 0087 Observation photos (4)

2.2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

10 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

15.4 ft. - Surface Reinforcement Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

560.2 ft. - Surface Reinforcement Corroded, from 11 to 01 o'clock, within 8 inches of joint: NO - BROKEN REBAR PRESENT