Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 5, 2021, 07:09 AM
  • 15 0612A1_15 0612_10042021_231420.mp4

Date
10/05/2021
W/O
916518
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00601
PipeID
P12548
Time
12:09 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9452
Sewer Name
15 DOUBLE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_916518_TV15205_OCT2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0612A1
Downstream MH
15 0612
Dir. of Survey
Downstream
Length Surveyed
44.1 ft.
Total Length
44.1 ft.
Structural Index
3
Structural Quick
3800
Structural Rating
24
O&M Index
2
O&M Quick
2800
O&M Rating
16
Overall Index
3
Overall Quick
Overall Rating
40
Pipe schematic from manhole 15 0612A1 to 15 0612
MH: 15 0612A1MH: 15 0612downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 0612A10 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 30 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start24.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"42.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish42.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish44.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0612, ABANDONED MH

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Downstream Manhole, Survey Ends - 15 0612, ABANDONED MH

    44.1 ft. - Downstream Manhole, Survey Ends - 15 0612, ABANDONED MH

Observations (9)

DistanceCodeObservation
24.7TFA
0AMH15 0612A1
2DAGS
44.1AMH15 0612, ABANDONED MH
42.3DAGS
0MWM
2SAP
42.3SAP
0MWL

Properties (7)

additional_info
630069100421202
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2021-10-05T00:09:19-07:00
documentation
PRO PIPE
is_lateral_inspection
false