Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 19, 2021, 05:54 AM
  • 14 0954_14 0953_10182021_221236.mp4

Date
10/18/2021
W/O
916874
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00957
PipeID
P23170
Time
10:54 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9467
Sewer Name
14 AVENUE "H" WEST TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
05
Purpose
Routine Assessment
Project
WO_916874_TV14044_OCT2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
14 0953
Downstream MH
14 0954
Dir. of Survey
Upstream
Length Surveyed
505.6 ft.
Total Length
505.6 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2R00
O&M Rating
192
Overall Index
2
Overall Quick
Overall Rating
192
Pipe schematic from manhole 14 0953 to 14 0954
MH: 14 0953MH: 14 0954upstream0 ft. AMH - Upstream Manhole, Survey Ends - 14 09542.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish484.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start505.6 ft. MWL - Water Level, 5 %of cross sectional area505.6 ft. MWM - Water Mark, 5 %of cross sectional area505.6 ft. AMH - Downstream Manhole, Survey Begins - 14 0953

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    20.7 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (6)

DistanceCodeObservation
502.9DAGS
20.7DAGS
0MWL
0MWM
0AMH14 0953
505.6AMH14 0954

Properties (7)

additional_info
630069101821201
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2021-10-18T22:54:57-07:00
documentation
PRO PIPE
is_lateral_inspection
false