Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 19, 2021, 06:16 AM
  • 14 0953_14 0952_10182021_223009.mp4

Date
10/18/2021
W/O
916874
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00957
PipeID
P23169
Time
11:16 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9467
Sewer Name
14 AVENUE "H" WEST TRUNK
City
LANCASTER
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
05
Purpose
Routine Assessment
Project
WO_916874_TV14044_OCT2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
30 in.
Width
30 in.
Upstream MH
14 0953
Downstream MH
14 0952
Dir. of Survey
Downstream
Length Surveyed
505.2 ft.
Total Length
505.2 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2J00
O&M Rating
106
Overall Index
2
Overall Quick
Overall Rating
106
Pipe schematic from manhole 14 0953 to 14 0952
MH: 14 0953MH: 14 0952downstream0 ft. AMH - Upstream Manhole, Survey Begins - 14 09530 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area238.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start498.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"501.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish505.2 ft. AMH - Downstream Manhole, Survey Ends - 14 0952

Observation photos (1)

  • Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock,  , within 8 inches of joint: YES, Start

    238.3 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

Observations (7)

DistanceCodeObservation
0AMH14 0953
238.3DAGS
0MWL
501.8DAGS
505.2AMH14 0952
0MWM
498.2TF

Properties (7)

additional_info
630069101821201
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2021-10-18T23:16:48-07:00
documentation
PRO PIPE
is_lateral_inspection
false