Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 13, 2021, 06:26 AM
  • 14 0586A_14 0586_10122021_223125.mp4

Date
10/12/2021
W/O
916873
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00572
PipeID
P18676
Time
11:26 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9461
Sewer Name
14 DIVISION STREET TRUNK
City
LANCASTER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
23
Purpose
Routine Assessment
Project
WO_916873_TV14008_OCT2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
14 0586A
Downstream MH
14 0586
Dir. of Survey
Downstream
Length Surveyed
110.4 ft.
Total Length
110.4 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
2C00
O&M Rating
42
Overall Index
2
Overall Quick
Overall Rating
42
Pipe schematic from manhole 14 0586A to 14 0586
MH: 14 0586AMH: 14 0586downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 14 0586A2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start108.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Finish110.4 ft. AMH - Downstream Manhole, Survey Ends - 14 0586

Observation photos (1)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (8)

DistanceCodeObservation
110.4AMH14 0586
0MWM
108.3DAGS
0MWL
0MGOCONNECTION AT MH 9 O'CLOCK
0MGOCOCKROACHES IN MANHOLE
0AMH14 0586A
2DAGS

Properties (8)

additional_info
630069101221201
custom_field_three
LIGHT GREASE
custom_field_two
4
customer
1
datetime
2021-10-12T23:26:35-07:00
documentation
PRO PIPE
is_lateral_inspection
false
year_laid
29761