Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 20, 2021, 06:58 AM
  • 14 0458_14 0457_10192021_231455.mp4

Date
10/19/2021
W/O
916871
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00570
PipeID
P18546
Time
11:58 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9468
Sewer Name
14 AVENUE "I" TRUNK
City
LANCASTER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
11
Purpose
Routine Assessment
Project
WO_916871_TV14045_OCT2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
14 0458
Downstream MH
14 0457
Dir. of Survey
Downstream
Length Surveyed
384.6 ft.
Total Length
384.6 ft.
Structural Index
3
Structural Quick
3H22
Structural Rating
139
O&M Index
2
O&M Quick
2N00
O&M Rating
152
Overall Index
2
Overall Quick
Overall Rating
291
Pipe schematic from manhole 14 0458 to 14 0457
MH: 14 0458MH: 14 0457downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 14 04582 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start14.8 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"17.8 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"59.4 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"62 ft. TF - Tap Factory Made, at 09 o'clock, -, within 8 inches of joint: NO, 6"106.5 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"109.1 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"146.5 ft. CL - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES146.5 ft. CS - Crack Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES158.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start159.7 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"162.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"210.2 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"257.8 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"260.3 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"307.6 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"310.2 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"373 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"376 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"382.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish382.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish384.6 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK384.6 ft. AMH - Downstream Manhole, Survey Ends - 14 0457

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

    146.5 ft. - Crack Longitudinal, at 10 o'clock, within 8 inches of joint: YES

  • Crack Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES

    146.5 ft. - Crack Spiral, from 01 to 03 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    158.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (28)

DistanceCodeObservation
62TF
159.7TFC
0MWM
106.5TFC
0MGOCONNECTION AT MH 9 O'CLOCK
373TFC
14.8TFC
146.5CL
0MWL
384.6MGOCONNECTION AT MH 9 O'CLOCK
0MGOCOCKROACHES IN MANHOLE
376TFC
109.1TFC
146.5CS
384.6AMH14 0457
310.2TFC
382.9DAGS
382.9CM
2DAGS
162.2TFC
59.4TFC
257.8TFC
307.6TFC
0AMH14 0458
158.1CM
17.8TFC
260.3TFC
210.2TFC

Properties (7)

additional_info
630069101921201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-10-19T23:58:45-07:00
documentation
PRO PIPE
is_lateral_inspection
false