- Date
- 10/14/2021
- W/O
- 916726
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00169
- PipeID
- P11215
- Time
- 2:01 AM
- Certificate
- U-508-7069
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K9445
- Sewer Name
- H JOINT OUTFALL H - UNIT 2C
- City
- BELL GARDENS
- Loc. details
- Light Highway
- Location Code
- C
- Use of Sewer
- Sanitary Sewer
- District
- District 02
- Page No.
- 23
- Purpose
- Routine Assessment
- Project
- WO_916726_TV02168_OCT2021
- Sewer Type
- Gravity
- Material
- Reinforced Concrete Pipe
- Shape
- Circular
- Height
- 36 in.
- Width
- 36 in.
- Upstream MH
- H 0191
- Downstream MH
- H 0190
- Dir. of Survey
- Downstream
- Length Surveyed
- 428.9 ft.
- Total Length
- 428.9 ft.
- Structural Index
- 3
- Structural Quick
- 3P2P
- Structural Rating
- 425
- O&M Index
- 2
- O&M Quick
- 2100
- O&M Rating
- 2
- Overall Index
- 3
- Overall Quick
- —
- Overall Rating
- 427
Pipe schematic from manhole H 0191 to H 0190 Observation photos (3)

2.3 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

204.8 ft. - Tap Factory Made Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 1"