Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 21, 2021, 08:41 AM
  • 05 2630_05 2629_10212021_015156.mp4

Date
10/21/2021
W/O
916329
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01145
PipeID
P25721
Time
1:41 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9507
Sewer Name
05 MANCHESTER AVENUE PUMP RELIEF TRUNK
City
HAWTHRONE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
14
Purpose
Routine Assessment
Project
WO_916329_TV05191_OCT2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
05 2630
Downstream MH
05 2629
Dir. of Survey
Downstream
Length Surveyed
350 ft.
Total Length
350 ft.
Structural Index
3
Structural Quick
3M2M
Structural Rating
345
O&M Index
2
O&M Quick
2M00
O&M Rating
138
Overall Index
2
Overall Quick
Overall Rating
483
Pipe schematic from manhole 05 2630 to 05 2629
MH: 05 2630MH: 05 2629downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 26300 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start347 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish347 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish347 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish350 ft. AMH - Downstream Manhole, Survey Ends - 05 2629

Observations (10)

DistanceCodeObservation
0MWM
2SSS
0AMH05 2630
347SSS
0MWL
2DAGS
347DAGS
350AMH05 2629
347CM
2CM

Properties (7)

additional_info
630074102021204
custom_field_three
SPALLING
custom_field_two
3
customer
1
datetime
2021-10-21T01:41:58-07:00
documentation
PROPIPE
is_lateral_inspection
false