Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 21, 2021, 10:34 AM
  • 05 2625_05 2624_10212021_034448.mp4

Date
10/21/2021
W/O
916329
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z01145
PipeID
P25716
Time
3:34 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9507
Sewer Name
05 MANCHESTER AVENUE PUMP RELIEF TRUNK
City
HAWTHRONE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
14
Purpose
Routine Assessment
Project
WO_916329_TV05191_OCT2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
05 2625
Downstream MH
05 2624
Dir. of Survey
Downstream
Length Surveyed
415.7 ft.
Total Length
415.7 ft.
Structural Index
3
Structural Quick
3P2O
Structural Rating
413
O&M Index
2
O&M Quick
2O00
O&M Rating
164
Overall Index
2
Overall Quick
Overall Rating
577
Pipe schematic from manhole 05 2625 to 05 2624
MH: 05 2625MH: 05 2624downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 26250 ft. MWL - Water Level, 15 %of cross sectional area2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start410.7 ft. FL - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES413 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish413 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish413 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish415.7 ft. AMH - Downstream Manhole, Survey Ends - 05 2624

Observation photos (1)

  • Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

    410.7 ft. - Fracture Longitudinal, at 01 o'clock, within 8 inches of joint: YES

Observations (11)

DistanceCodeObservation
2SSS
0MWM
413CM
415.7AMH05 2624
2DAGS
0AMH05 2625
2CM
410.7FL
413SSS
0MWL
413DAGS

Properties (7)

additional_info
630074102021204
custom_field_three
NO SEVERE DEFECTS
custom_field_two
3
customer
1
datetime
2021-10-21T03:34:29-07:00
documentation
PROPIPE
is_lateral_inspection
false