Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 13, 2021, 09:58 AM
  • 02 1261_02 2317_10132021_030927.mp4

Date
10/13/2021
W/O
916623
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00288
PipeID
P08498
Time
2:58 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9443
Sewer Name
02 MONTEREY PARK DIVERSION TRUNK
City
MONTEREY PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
WO_916623_TV02100_OCT2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
30 in.
Upstream MH
02 1261
Downstream MH
02 2317
Dir. of Survey
Downstream
Length Surveyed
301.9 ft.
Total Length
301.9 ft.
Structural Index
3
Structural Quick
3K2K
Structural Rating
300
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
300
Pipe schematic from manhole 02 1261 to 02 2317
MH: 02 1261MH: 02 2317downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 12610 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area3.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start3.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start301.9 ft. MGO - General Observation - CONNECTION AT THE MH 12 OC'LOCK301.9 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish301.9 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK301.9 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish301.9 ft. AMH - Downstream Manhole, Survey Ends - 02 2317

Observation photos (2)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.6 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.6 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
0AMH02 1261
3.6SSS
301.9MGOCONNECTION AT THE MH 12 OC'LOCK
3.6SAP
301.9SAP
301.9MGOCONNECTION AT THE MH 3 OC'LOCK
301.9SSS
0MWM
301.9AMH02 2317
0MWL

Properties (7)

additional_info
630074101221202
custom_field_three
AGGREGATE PROJECTING/SPALLING
custom_field_two
2
customer
1
datetime
2021-10-13T02:58:24-07:00
documentation
PROPIPE
is_lateral_inspection
false