Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 13, 2021, 10:38 AM
  • 02 1265_02 1264_10132021_034930.mp4

Date
10/13/2021
W/O
916623
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00288
PipeID
P04671
Time
3:38 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9443
Sewer Name
02 MONTEREY PARK DIVERSION TRUNK
City
MONTEREY PARK
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
WO_916623_TV02100_OCT2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
18 in.
Upstream MH
02 1265
Downstream MH
02 1264
Dir. of Survey
Downstream
Length Surveyed
277.6 ft.
Total Length
277.6 ft.
Structural Index
3
Structural Quick
3J2I
Structural Rating
267
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
267
Pipe schematic from manhole 02 1265 to 02 1264
MH: 02 1265MH: 02 1264downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 12650 ft. MWL - Water Level, 15 %of cross sectional area2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start21 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start277.6 ft. AMH - Downstream Manhole, Survey Ends - 02 1264277.6 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish277.6 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    21 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (8)

DistanceCodeObservation
277.6AMH02 1264
277.6SAP
0MWM
21SSS
2.1SAP
0AMH02 1265
277.6SSS
0MWL

Properties (7)

additional_info
630074101221202
custom_field_three
AGGREGATE PROJECTING/SPALLING
custom_field_two
2
customer
1
datetime
2021-10-13T03:38:32-07:00
documentation
PROPIPE
is_lateral_inspection
false