Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 28, 2021, 07:55 AM
  • C 0345_C 0344_10282021_012808.mp4

Date
10/28/2021
W/O
916501
Weather
Dry
Operator/Surveyor
J. BUENROSTRO
Sewer ID
Z00138
PipeID
P09808
Time
12:55 AM
Certificate
U-715-07000770
System Owner
1
Date Cleaned
Pre-Cleaning
Not Known
Media Label
K9267
Sewer Name
C JOINT OUTFALL C - UNIT 7B
City
LONG BEACH
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 03
Page No.
17
Purpose
Routine Assessment
Project
RFIR_WO_916501_TV03115_OCT2021
Sewer Type
Gravity
Material
Reinforced Concrete Pipe
Shape
Circular
Height
33 in.
Width
15 in.
Upstream MH
C 0344
Downstream MH
C 0345
Dir. of Survey
Upstream
Length Surveyed
456.5 ft.
Total Length
456.5 ft.
Structural Index
3
Structural Quick
583Q
Structural Rating
489
O&M Index
1
O&M Quick
1A00
O&M Rating
11
Overall Index
3
Overall Quick
Overall Rating
500
Pipe schematic from manhole C 0344 to C 0345
MH: C 0344MH: C 0345upstream0 ft. AMH - Upstream Manhole, Survey Ends - C 03451 ft. MGO - General Observation - STOP LOG AT U/S MH1.7 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.7 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish1.7 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish37.4 ft. SRV - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start52.2 ft. SRV - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO135.4 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6"401.1 ft. LR - Alignment Right, 10 %, Finish402.2 ft. MGO - General Observation - MAG COATING448 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start454.2 ft. LR - Alignment Right, 10 %, Start454.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start456.4 ft. MWM - Water Mark, 25 %of cross sectional area456.5 ft. MWL - Water Level, 20 %of cross sectional area456.5 ft. AMH - Downstream Manhole, Survey Begins - C 0344

Observation photos (5)

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Alignment Right, 10 %, Start

    2.3 ft. - Alignment Right, 10 %, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    8.5 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO

    404.3 ft. - Surface Reinforcement Visible, from 11 to 01 o'clock, within 8 inches of joint: NO

  • Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    419.1 ft. - Surface Reinforcement Visible, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

Observations (16)

DistanceCodeObservation
321.1TB
8.5SAP
0MWL
55.4LR
2.2SSS
454.8SSS
419.1SRV
54.3MGOMAG COATING
2.3LR
455.5MGOSTOP LOG AT U/S MH
0AMHC 0344
454.8SAP
404.3SRV
454.8SRV
0.1MWM
456.5AMHC 0345

Properties (7)

additional_info
630074102721202
custom_field_three
REINFORCEMENT VISIBLE
custom_field_two
2
customer
1
datetime
2021-10-28T00:55:46-07:00
documentation
PROPIPE
is_lateral_inspection
false