Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 25, 2021, 07:47 AM
  • 05 1045_05 0115_10252021_010824.mp4

Date
10/25/2021
W/O
916412
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00441
PipeID
P06280
Time
12:47 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9510
Sewer Name
05 FLOWER STREET TRUNK
City
HAWTHRONE
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_916412_TV05195_OCT2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
10 in.
Upstream MH
05 1045
Downstream MH
05 0115
Dir. of Survey
Downstream
Length Surveyed
330.3 ft.
Total Length
330.3 ft.
Structural Index
4
Structural Quick
514K
Structural Rating
261
O&M Index
2
O&M Quick
3112
O&M Rating
5
Overall Index
4
Overall Quick
Overall Rating
266
Pipe schematic from manhole 05 1045 to 05 0115
MH: 05 1045MH: 05 0115downstream0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - 05 10450 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK3.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start5.5 ft. RFJ - Roots Fine Joint, at 03 o'clock, within 8 inches of joint: YES9.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"11.2 ft. B - Broken, from 08 to 10 o'clock, within 8 inches of joint: YES12.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"41.2 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start41.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish52.4 ft. TBI - Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 1"56.4 ft. RFJ - Roots Fine Joint, from 03 to 05 o'clock, within 8 inches of joint: YES82.5 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"124.9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"136.6 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"139.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"184.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"205.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"208.6 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"253.9 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"255.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"292.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"294.9 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"330.3 ft. AMH - Downstream Manhole, Survey Ends - 05 0115330.3 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK330.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (8)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.1 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    9.7 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Broken, from 08 to 10 o'clock, within 8 inches of joint: YES

    11.2 ft. - Broken, from 08 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    41.2 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

    52.4 ft. - Tap Break-In Intruding, at 02 o'clock, -, -, within 8 inches of joint: NO, 6", 1"

  • Roots Fine Joint, from 03 to 05 o'clock, within 8 inches of joint: YES

    56.4 ft. - Roots Fine Joint, from 03 to 05 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    82.5 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    208.6 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (28)

DistanceCodeObservation
205.7TFC
82.5TB
253.9TF
294.9TFC
292.2TF
41.2FM
12.5TF
3.1CM
136.6TFC
208.6TB
0MWM
330.3AMH05 0115
330.3MGOCONNECTION AT THE MH 9 OC'LOCK
0MGOCONNECTION AT THE MH 9 OC'LOCK
56.4RFJ
11.2B
52.4TBI
139.1TF
124.9TFC
330.3FM
9.7TB
184.7TF
0AMH05 1045
5.5RFJ
0MWL
41.2CM
0MGOCONNECTION AT THE MH 3 OC'LOCK
255.9TF

Properties (7)

additional_info
630074102521001
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-10-25T00:47:13-07:00
documentation
PROPIPE
is_lateral_inspection
false