Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 25, 2021, 08:30 AM
  • 05 0899_05 0898_10252021_014733.mp4

Date
10/25/2021
W/O
916505
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00512
PipeID
P06129
Time
1:30 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9511
Sewer Name
05 RAYMOND AVENUE TRUNK
City
HAWTHRONE
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
13
Purpose
Routine Assessment
Project
RFIR_WO_916505_TV05204_OCT2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 0899
Downstream MH
05 0898
Dir. of Survey
Downstream
Length Surveyed
317.2 ft.
Total Length
317.2 ft.
Structural Index
3
Structural Quick
413L
Structural Rating
193
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
193
Pipe schematic from manhole 05 0899 to 05 0898
MH: 05 0899MH: 05 0898downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - 05 08990 ft. MWL - Water Level, 10 %of cross sectional area3.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start21.2 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"68.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"81.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"83.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"116.4 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"126.7 ft. FM - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES127.7 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"146.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"162.2 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"174 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"207.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"222 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"237.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"258.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"288.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"290.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"301.3 ft. TB - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"317.1 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish317.2 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK317.2 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK317.2 ft. AMH - Downstream Manhole, Survey Ends - 05 0898

Observation photos (7)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    3.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    81.7 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

    126.7 ft. - Fracture Multiple, from 01 to 04 o'clock, within 8 inches of joint: YES

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    127.7 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    174 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    222 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    301.3 ft. - Tap Break-In, at 02 o'clock, -, within 8 inches of joint: NO, 6"

Observations (26)

DistanceCodeObservation
127.7TB
0MWM
21.2TF
237.8TF
162.2TFC
126.7FM
207.7TFC
258.1TFC
146.8TF
3.6CM
317.2MGOCONNECTION AT THE MH 9 OC'LOCK
68.5TFC
288.7TF
0MGOCONNECTION AT THE MH 3 OC'LOCK
222TB
0AMH05 0899
0MWL
301.3TB
81.7TB
290.6TFC
174TB
317.1CM
317.2MGOCONNECTION AT THE MH 3 OC'LOCK
317.2AMH05 0898
116.4TFC
83.6TF

Properties (7)

additional_info
630074102521002
custom_field_three
MULTIPLE CRACKS
custom_field_two
3
customer
1
datetime
2021-10-25T01:30:03-07:00
documentation
PROPIPE
is_lateral_inspection
false