Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 4, 2021, 10:27 AM
  • 04 0114A_04 0114_10042021_034045.mp4

Date
10/04/2021
W/O
916630
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00411
PipeID
P11850
Time
3:27 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9399
Sewer Name
04 LA BREA AVENUE TRUNK
City
WEST HOLLYWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
02
Purpose
Routine Assessment
Project
WO_916630_TV04018_OCT2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
12 in.
Width
12 in.
Upstream MH
04 0114A
Downstream MH
04 0114
Dir. of Survey
Downstream
Length Surveyed
237 ft.
Total Length
237 ft.
Structural Index
4
Structural Quick
4F3A
Structural Rating
174
O&M Index
1
O&M Quick
1200
O&M Rating
2
Overall Index
4
Overall Quick
Overall Rating
176
Pipe schematic from manhole 04 0114A to 04 0114
MH: 04 0114AMH: 04 0114downstream0 ft. AMH - Upstream Manhole, Survey Begins - 04 0114A0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 5 %of cross sectional area4 ft. CM - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Start15.7 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"26.5 ft. RFJ - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR28 ft. TFA - Tap Factory Made Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"35.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"54.5 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Start54.5 ft. CM - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Finish85.7 ft. RFJ - Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YESR86.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"93.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"130.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"173.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"203.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"235.5 ft. FM - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Finish237 ft. MGO - General Observation - COCKROACHES IN MANHOLE237 ft. AMH - Downstream Manhole, Survey Ends - 04 0114

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

    4 ft. - Crack Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR

    26.5 ft. - Roots Fine Joint, from 09 to 03 o'clock, within 8 inches of joint: YESR

  • Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

    54.5 ft. - Fracture Multiple, from 12 to 12 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YESR

    85.7 ft. - Roots Fine Joint, from 07 to 09 o'clock, within 8 inches of joint: YESR

  • General Observation - COCKROACHES IN MANHOLE

    237 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (20)

DistanceCodeObservation
0AMH04 0114A
35.5TFA
0MGOCOCKROACHES IN MANHOLE
237MGOCOCKROACHES IN MANHOLE
85.7RFJ
28TFA
93.7TFA
235.5FM
237AMH04 0114
26.5RFJ
54.5FM
0MWL
15.7TFA
203.2TF
86.5TFA
54.5CM
173.1TFA
0MWM
4CM
130.5TFA

Properties (7)

additional_info
630069100421002
custom_field_three
CRACKS/FRACTURES
custom_field_two
2
customer
1
datetime
2021-10-04T03:27:37-07:00
documentation
PRO PIPE
is_lateral_inspection
false