Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 8, 2021, 05:18 AM
  • 02 1824_02 1823A_10072021_222315.mp4

Date
10/07/2021
W/O
916506
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00236
PipeID
P25919
Time
10:18 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9437
Sewer Name
02 ATLANTIC AVENUE RELIEF TRUNK
City
E. LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_916506_TV02017_OCT2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
18 in.
Upstream MH
02 1824
Downstream MH
02 1823A
Dir. of Survey
Downstream
Length Surveyed
66.5 ft.
Total Length
66.5 ft.
Structural Index
3
Structural Quick
3B2B
Structural Rating
65
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
65
Pipe schematic from manhole 02 1824 to 02 1823A
MH: 02 1824MH: 02 1823Adownstream0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 18242.1 ft. MGO - General Observation - MAG COAT2.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.1 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start66.5 ft. AMH - Downstream Manhole, Survey Ends - 02 1823A66.5 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish66.5 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish66.5 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK

Observation photos (2)

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.1 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
66.5AMH02 1823A
0MWL
2.1MGOMAG COAT
66.5SSS
0MWM
66.5SAP
66.5MGOCONNECTION AT THE MH 3 OC'LOCK
2.1SAP
0AMH02 1824
2.1SSS

Properties (8)

additional_info
630074100721201
custom_field_three
AGGREGATE PROJECTING/SPALLING
custom_field_two
2
customer
1
datetime
2021-10-07T22:18:30-07:00
documentation
PROPIPE
is_lateral_inspection
false
year_laid
39052