Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 8, 2021, 04:54 AM
  • 02 1178_02 1825_10072021_220419.mp4

Date
10/07/2021
W/O
916506
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00236
PipeID
P04173
Time
9:54 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9437
Sewer Name
02 ATLANTIC AVENUE RELIEF TRUNK
City
E. LOS ANGELES
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
09
Purpose
Routine Assessment
Project
RFIR_WO_916506_TV02017_OCT2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
18 in.
Width
15 in.
Upstream MH
02 1178
Downstream MH
02 1825
Dir. of Survey
Downstream
Length Surveyed
54.6 ft.
Total Length
54.6 ft.
Structural Index
3
Structural Quick
3A2A
Structural Rating
53
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
53
Pipe schematic from manhole 02 1178 to 02 1825
MH: 02 1178MH: 02 1825downstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 11780 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK2.2 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2.2 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start26.3 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start26.3 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish53.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish54.4 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish54.6 ft. AMH - Downstream Manhole, Survey Ends - 02 1825

Observation photos (3)

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2.2 ft. - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    26.3 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (11)

DistanceCodeObservation
53.3SSS
54.4SAP
0MWM
0AMH02 1178
0MWL
0MGOCONNECTION AT THE MH 9 OC'LOCK
26.3SAP
2.2SAV
54.6AMH02 1825
26.3SAV
2.2SSS

Properties (7)

additional_info
630074100721201
custom_field_three
AGGREGATE PROJECTING/SPALLING
custom_field_two
2
customer
1
datetime
2021-10-07T21:54:05-07:00
documentation
PROPIPE
is_lateral_inspection
false