Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 5, 2021, 06:36 AM
  • 15 0613_15 0612A_10042021_224454.mp4

Date
10/04/2021
W/O
916518
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00601
PipeID
P12549
Time
11:36 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9452
Sewer Name
15 DOUBLE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_916518_TV15205_OCT2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0613
Downstream MH
15 0612A
Dir. of Survey
Downstream
Length Surveyed
137.5 ft.
Total Length
137.5 ft.
Structural Index
3
Structural Quick
3D00
Structural Rating
81
O&M Index
2
O&M Quick
2D00
O&M Rating
54
Overall Index
3
Overall Quick
Overall Rating
135
Pipe schematic from manhole 15 0613 to 15 0612A
MH: 15 0613MH: 15 0612Adownstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 06130 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start30.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"35.9 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"96.5 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"127.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"135.1 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish135.1 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish137.5 ft. AMH - Downstream Manhole, Survey Ends - 15 0612A137.5 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK137.5 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (4)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    137.5 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (15)

DistanceCodeObservation
127.1TFA
2DAGS
2SAP
137.5AMH15 0612A
0AMH15 0613
137.5MGOCONNECTION AT MH 3 O'CLOCK
30.6TF
0MWM
35.9TFA
0MGOCOCKROACHES IN MANHOLE
135.1SAP
96.5TF
0MWL
135.1DAGS
137.5MGOCOCKROACHES IN MANHOLE

Properties (7)

additional_info
630069100421202
custom_field_three
PROJECTING AGGREGATE
custom_field_two
3
customer
1
datetime
2021-10-04T23:36:51-07:00
documentation
PRO PIPE
is_lateral_inspection
false