Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 5, 2021, 07:15 AM
  • 15 0612_15 0611_10042021_232545.mp4

Date
10/05/2021
W/O
916518
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00601
PipeID
P12547
Time
12:15 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9452
Sewer Name
15 DOUBLE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_916518_TV15205_OCT2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0612
Downstream MH
15 0611
Dir. of Survey
Downstream
Length Surveyed
136 ft.
Total Length
136 ft.
Structural Index
3
Structural Quick
423D
Structural Rating
86
O&M Index
2
O&M Quick
2D00
O&M Rating
52
Overall Index
3
Overall Quick
Overall Rating
138
Pipe schematic from manhole 15 0612 to 15 0611
MH: 15 0612MH: 15 0611downstream0 ft. AMH - Upstream Manhole, Survey Begins - 15 0612, ABANDONED MH0 ft. MWL - Water Level, 20 %of cross sectional area0 ft. MWM - Water Mark, 35 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES20.7 ft. TB - Tap Break-In, at 10 o'clock, -, within 8 inches of joint: NO, 6", 6"23.4 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"54.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES80.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"95.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"133.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish133.8 ft. SAP - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish136 ft. MGO - General Observation - COCKROACHES IN MANHOLE136 ft. AMH - Downstream Manhole, Survey Ends - 15 0611136 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK

Observation photos (6)

  • Upstream Manhole, Survey Begins - 15 0612, ABANDONED MH

    0 ft. - Upstream Manhole, Survey Begins - 15 0612, ABANDONED MH

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    54.6 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    136 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (16)

DistanceCodeObservation
136MGOCOCKROACHES IN MANHOLE
0AMH15 0612, ABANDONED MH
95.1TFC
0MWL
136AMH15 0611
133.8DAGS
20.7TB
2DAGS
136MGOCONNECTION AT MH 3 O'CLOCK
7FM
54.6FM
80.3TFA
2SAP
23.4TFA
0MWM
133.8SAP

Properties (7)

additional_info
630069100421202
custom_field_three
FRACTURES/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2021-10-05T00:15:21-07:00
documentation
PRO PIPE
is_lateral_inspection
false