Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 5, 2021, 07:50 AM
  • 15 0610_15 0609A_10052021_000335.mp4

Date
10/05/2021
W/O
916518
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00601
PipeID
P12544
Time
12:50 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9452
Sewer Name
15 DOUBLE AVENUE TRUNK
City
TEMPLE CITY
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
11
Purpose
Routine Assessment
Project
RFIR_WO_916518_TV15205_OCT2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
15 0610
Downstream MH
15 0609A
Dir. of Survey
Downstream
Length Surveyed
229.1 ft.
Total Length
229.1 ft.
Structural Index
3
Structural Quick
4G3H
Structural Rating
302
O&M Index
2
O&M Quick
2H00
O&M Rating
90
Overall Index
3
Overall Quick
Overall Rating
392
Pipe schematic from manhole 15 0610 to 15 0609A
MH: 15 0610MH: 15 0609Adownstream0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 15 06100 ft. MGO - General Observation - MAG COAT0 ft. MWL - Water Level, 10 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start7.1 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start11.2 ft. CL - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES18.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start67.8 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: NO, 6"94.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"152.3 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6", 6"185.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"226.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish226.8 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish226.8 ft. SAV - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish229.1 ft. MGO - General Observation - CONNECTION AT MH 9 O'CLOCK229.1 ft. AMH - Downstream Manhole, Survey Ends - 15 0609A

Observation photos (4)

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7.1 ft. - Surface Aggregate Visible, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

    11.2 ft. - Crack Longitudinal, at 12 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    18.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
152.3TF
0MWM
18.6FM
185.3TFC
0AMH15 0610
226.8FM
226.8DAGS
11.2CL
0MGOMAG COAT
0MWL
229.1MGOCONNECTION AT MH 9 O'CLOCK
67.8TFA
226.8SAV
94.7TFC
7.1SAV
229.1AMH15 0609A
2DAGS

Properties (7)

additional_info
630069100421202
custom_field_three
FRACTURES/VISIBLE AGGREGATE
custom_field_two
2
customer
1
datetime
2021-10-05T00:50:53-07:00
documentation
PRO PIPE
is_lateral_inspection
false