Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 28, 2021, 06:00 AM
  • H 0647_H 0646_09272021_221736.mp4

Date
09/27/2021
W/O
916369
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00192
PipeID
P11053
Time
11:00 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9384
Sewer Name
H JOINT OUTFALL H - UNIT 8J
City
WEST COVINA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
24
Purpose
Routine Assessment
Project
RFIR_WO_916369_TV15166_OCT2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
H 0647
Downstream MH
H 0646
Dir. of Survey
Downstream
Length Surveyed
341.1 ft.
Total Length
341.1 ft.
Structural Index
3
Structural Quick
3L2G
Structural Rating
279
O&M Index
2
O&M Quick
2L00
O&M Rating
134
Overall Index
2
Overall Quick
Overall Rating
413
Pipe schematic from manhole H 0647 to H 0646
MH: H 0647MH: H 0646downstream0 ft. AMH - Upstream Manhole, Survey Begins - H 06470 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MGO - General Observation - COCKROACHES IN MANHOLE2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start2 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start51.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"55.1 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"99.3 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"144.2 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start145 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"169.4 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"202.9 ft. TBA - Tap Break-In Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"287.5 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"307.7 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"338.7 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish338.7 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish338.7 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish341.1 ft. AMH - Downstream Manhole, Survey Ends - H 0646341.1 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK341.1 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (6)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    144.2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

    145 ft. - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"

  • General Observation - COCKROACHES IN MANHOLE

    341.1 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (22)

DistanceCodeObservation
51.1TFC
0AMHH 0647
341.1AMHH 0646
0MWM
144.2SSS
338.7SSS
0MWL
341.1MGOCONNECTION AT MH 3 O'CLOCK
307.7TFA
0MGOCONNECTION AT MH 3 O'CLOCK
202.9TBA
2DAGS
338.7SAP
0MGOCOCKROACHES IN MANHOLE
287.5TFA
99.3TFA
341.1MGOCOCKROACHES IN MANHOLE
169.4TFC
55.1TFA
145TF
338.7DAGS
2SAP

Properties (7)

additional_info
630069092721202
custom_field_three
SPALLING/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2021-09-27T23:00:46-07:00
documentation
PRO PIPE
is_lateral_inspection
false