Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 27, 2021, 10:51 AM
  • 04 0049A_04 0049_09272021_040344.mp4

Date
09/27/2021
W/O
916397
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00412
PipeID
P11779
Time
3:51 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9382
Sewer Name
04 LA CIENEGA BOULEVARD TRUNK
City
WEST HOLLYWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
03
Purpose
Routine Assessment
Project
RFIR_WO_916397_TV04019_OCT2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
04 0049A
Downstream MH
04 0049
Dir. of Survey
Downstream
Length Surveyed
155.4 ft.
Total Length
155.4 ft.
Structural Index
3
Structural Quick
513E
Structural Rating
95
O&M Index
2
O&M Quick
2E00
O&M Rating
60
Overall Index
3
Overall Quick
Overall Rating
155
Pipe schematic from manhole 04 0049A to 04 0049
MH: 04 0049AMH: 04 0049downstream0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. AMH - Upstream Manhole, Survey Begins - 04 0049A0 ft. MGO - General Observation - CONNECTION AT MH 3 O'CLOCK0 ft. MWM - Water Mark, 35 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.9 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start7.2 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"43.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"45.8 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"45.8 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"87.4 ft. TFA - Tap Factory Made Active, at 10 o'clock, -, within 8 inches of joint: NO, 6"90.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"129.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"139 ft. HSV - Hole Soil Visible, from 11 to 01 o'clock, within 8 inches of joint: NO140.3 ft. TBA - Tap Break-In Active, at 12 o'clock, -, within 8 inches of joint: NO, 6"142.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"153.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish153.4 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish155.4 ft. AMH - Downstream Manhole, Survey Ends - 04 0049155.4 ft. MGO - General Observation - COCKROACHES IN MANHOLE

Observation photos (5)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.9 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Hole Soil Visible, from 11 to 01 o'clock, within 8 inches of joint: NO

    139 ft. - Hole Soil Visible, from 11 to 01 o'clock, within 8 inches of joint: NO

  • General Observation - COCKROACHES IN MANHOLE

    155.4 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (21)

DistanceCodeObservation
87.4TFA
2DAGS
90.5TFA
0MGOCOCKROACHES IN MANHOLE
153.4CM
0AMH04 0049A
153.4DAGS
129.8TFC
0MGOCONNECTION AT MH 3 O'CLOCK
45.8TBA
5.9CM
140.3TBA
155.4AMH04 0049
0MWM
45.8TFA
0MWL
142.5TFA
155.4MGOCOCKROACHES IN MANHOLE
43.5TFC
139HSV
7.2TFA

Properties (7)

additional_info
630069092721002
custom_field_three
HOLE/MULTIPLE CRACKS
custom_field_two
2
customer
1
datetime
2021-09-27T03:51:19-07:00
documentation
PRO PIPE
is_lateral_inspection
false