Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 30, 2021, 07:44 AM
  • 17 0007_17 0006_10302021_010031.mp4

Date
10/30/2021
W/O
0916849
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00668
PipeID
P13732
Time
12:44 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1994R
Sewer Name
17 DISTRICT #17 MAIN TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
07
Purpose
Maintenance Related
Project
20211027MDM_DISTRICT_17_MAIN_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
17 0007
Downstream MH
17 0006
Dir. of Survey
Downstream
Length Surveyed
277.7 ft.
Total Length
277.7 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
1
O&M Quick
1300
O&M Rating
3
Overall Index
1
Overall Quick
Overall Rating
3
Pipe schematic from manhole 17 0007 to 17 0006
MH: 17 0007MH: 17 0006downstream0 ft. MWM - Water Mark, 40 %of cross sectional area0 ft. MGO - General Observation - Conn. @ Mh, 9 O' Clock. Active0 ft. AMH - Upstream Manhole, Survey Begins - 12:50AM0 ft. MWL - Water Level, 10 %of cross sectional area8 ft. RFC - Roots Fine Connection, from 02 to 03 o'clock, within 8 inches of joint: YES - 1%76.4 ft. RFC - Roots Fine Connection, from 08 to 10 o'clock, within 8 inches of joint: YES - 3%80.3 ft. RFC - Roots Fine Connection, from 02 to 03 o'clock, within 8 inches of joint: YES - 1%277.7 ft. AMH - Downstream Manhole, Survey Ends - 1:05AM

Observations (8)

DistanceCodeObservation
0MWM
8RFC1%
0MGOConn. @ Mh, 9 O' Clock. Active
80.3RFC1%
277.7AMH1:05AM
0AMH12:50AM
0MWL
76.4RFC3%

Properties (5)

additional_info
ROOT EVALUATION ONLY
customer
LACSD
datetime
2021-10-30T00:44:01-07:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false