Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 29, 2021, 09:22 AM
  • 17 0009_17 008_10292021_022430.mp4

Date
10/29/2021
W/O
0916849
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00668
PipeID
P13734
Time
2:22 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1993R
Sewer Name
17 DISTRICT #17 MAIN TRUNK
City
PASADENA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 17
Page No.
07
Purpose
Maintenance Related
Project
20211027MDM_DISTRICT_17_MAIN_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
15 in.
Upstream MH
17 0009
Downstream MH
17 008
Dir. of Survey
Downstream
Length Surveyed
375.1 ft.
Total Length
375.1 ft.
Structural Index
0
Structural Quick
0000
Structural Rating
0
O&M Index
2
O&M Quick
3214
O&M Rating
10
Overall Index
2
Overall Quick
Overall Rating
10
Pipe schematic from manhole 17 0009 to 17 008
MH: 17 0009MH: 17 008downstream0 ft. AMH - Upstream Manhole, Survey Begins - 2:30AM0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 10 %of cross sectional area150.6 ft. RMC - Roots Medium Connection, from 08 to 10 o'clock, 5 %, within 8 inches of joint: YES170.8 ft. RFJ - Roots Fine Joint, from 12 to 03 o'clock, within 8 inches of joint: YESR - 3%185 ft. RFJ - Roots Fine Joint, from 01 to 04 o'clock, within 8 inches of joint: YESR - 2%204.2 ft. RMC - Roots Medium Connection, from 07 to 10 o'clock, 10 %, within 8 inches of joint: YES239 ft. RFC - Roots Fine Connection, from 09 to 10 o'clock, within 8 inches of joint: YES - 2%292.3 ft. RFC - Roots Fine Connection, from 09 to 10 o'clock, within 8 inches of joint: YES - 1%375.1 ft. AMH - Downstream Manhole, Survey Ends - 2:50AM

Observations (10)

DistanceCodeObservation
292.3RFC1%
0AMH2:30AM
185RFJ2%
375.1AMH2:50AM
150.6RMC
170.8RFJ3%
239RFC2%
204.2RMC
0MWM
0MWL

Properties (5)

additional_info
ROOT EVALUATION ONLY
customer
LACSD
datetime
2021-10-29T02:22:08-07:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection