Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Nov 2, 2021, 10:25 AM
  • 04 0088_04 0087_1122021_033414.mp4

Date
11/02/2021
W/O
092155
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00417
PipeID
P11826
Time
3:25 AM
Certificate
U-101406022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1997
Sewer Name
04 WARING AVENUE TRUNK
City
HOLLYWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 04
Page No.
01
Purpose
Routine Assessment
Project
20211102MDM_WARING_AVENUE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
04 0088
Downstream MH
04 0087
Dir. of Survey
Downstream
Length Surveyed
289.2 ft.
Total Length
289.2 ft.
Structural Index
2
Structural Quick
4135
Structural Rating
69
O&M Index
2
O&M Quick
3223
O&M Rating
14
Overall Index
2
Overall Quick
Overall Rating
83
Pipe schematic from manhole 04 0088 to 04 0087
MH: 04 0088MH: 04 0087downstream0 ft. MWL - Water Level, 5 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 3:25AM0 ft. MWM - Water Mark, 20 %of cross sectional area4 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - HAIRLINE7 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SLIGHT25.1 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H31.8 ft. FC - Fracture Circumferential, from 08 to 09 o'clock, within 8 inches of joint: YES - H36.8 ft. FC - Fracture Circumferential, from 11 to 04 o'clock, within 8 inches of joint: YES - S37.8 ft. TFA - Tap Factory Made Active, at 03 o'clock, -, within 8 inches of joint: YES, 6" - Active44.7 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL47.5 ft. FC - Fracture Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES - SL52.5 ft. FL - Fracture Longitudinal, at 12 o'clock, within 8 inches of joint: YES - H65.4 ft. FC - Fracture Circumferential, from 09 to 10 o'clock, within 8 inches of joint: YES - SL66.1 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open70.4 ft. RFJ - Roots Fine Joint, from 04 to 05 o'clock, within 8 inches of joint: YESR - 2%70.4 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL80.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H86.3 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SL93.5 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL103.8 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - H108.8 ft. RFJ - Roots Fine Joint, from 03 to 04 o'clock, within 8 inches of joint: YESR - 1%116.8 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - H117.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Active119.5 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL120.8 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open126.8 ft. FC - Fracture Circumferential, from 08 to 04 o'clock, within 8 inches of joint: YES - SL137.1 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL161.7 ft. TFD - Tap Factory Made Defective, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open-90% ROOTS161.7 ft. RMC - Roots Medium Connection, from 08 to 10 o'clock, 5 %, within 8 inches of joint: YES164 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-90% ROOTS173 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H182 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open192.9 ft. FL - Fracture Longitudinal, at 02 o'clock, within 8 inches of joint: YES - H200.3 ft. RMJ - Roots Medium Joint, from 02 to 05 o'clock, 5 %, within 8 inches of joint: YESR200.3 ft. TFD - Tap Factory Made Defective, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open-50% ROOTS204.1 ft. FC - Fracture Circumferential, from 09 to 11 o'clock, within 8 inches of joint: YES - SL206.6 ft. FL - Fracture Longitudinal, at 04 o'clock, within 8 inches of joint: YES - SL211.7 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL212.4 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open214.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - H234.7 ft. FC - Fracture Circumferential, from 09 to 03 o'clock, within 8 inches of joint: YES - SL245 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL250.2 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL251.4 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Open253.6 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Open255.1 ft. FC - Fracture Circumferential, from 07 to 08 o'clock, within 8 inches of joint: YES - SL263.3 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - H275.7 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL277.9 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - SL289.2 ft. AMH - Downstream Manhole, Survey Ends - 4:25AM

Observations (50)

DistanceCodeObservation
119.5FCSL
120.8TFOpen
212.4TFOpen
7FCSLIGHT
182TFOpen
277.9FCSL
0MWL
275.7FCSL
200.3RMJ
204.1FCSL
44.7FCSL
70.4RFJ2%
80.9FLH
253.6TFOpen
250.2FCSL
289.2AMH4:25AM
251.4TFOpen
108.8RFJ1%
37.8TFAActive
263.3FCH
86.3FCSL
93.5FCSL
0AMH3:25AM
126.8FCSL
206.6FLSL
161.7TFDOpen-90% ROOTS
47.5FCSL
70.4FCSL
255.1FCSL
0MWM
103.8FCH
164TFDOpen-90% ROOTS
31.8FCH
52.5FLH
245FCSL
66.1TFOpen
200.3TFDOpen-50% ROOTS
137.1FCSL
116.8FCH
173FCH
234.7FCSL
4FCHAIRLINE
65.4FCSL
36.8FCS
214.3FMH
192.9FLH
161.7RMC
25.1FLH
211.7FCSL
117.8TFActive

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2021-11-02T03:25:00-07:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false