Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 26, 2021, 10:27 AM
  • 14 0160_14 0159_08262021_035058.mp4

Date
08/26/2021
W/O
911937
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00584
PipeID
P18196
Time
3:27 AM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9245
Sewer Name
14 WEST SIDE TRUNK
City
LANCASTER
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 14
Page No.
10
Purpose
Routine Assessment
Project
RFIR_WO_911937_TV14035_SEP2021
Sewer Type
Gravity
Material
NRCP
Shape
Circular
Height
15 in.
Width
15 in.
Upstream MH
14 0159
Downstream MH
14 0160
Dir. of Survey
Upstream
Length Surveyed
447.9 ft.
Total Length
447.9 ft.
Structural Index
3
Structural Quick
3Q2Q
Structural Rating
445
O&M Index
2
O&M Quick
412Q
O&M Rating
182
Overall Index
2
Overall Quick
Overall Rating
627
Pipe schematic from manhole 14 0159 to 14 0160
MH: 14 0159MH: 14 0160upstream0 ft. AMH - Upstream Manhole, Survey Ends - 14 01600 ft. MGO - General Observation - CONN @ MH 12 AND 1 O'CLOCK/ACTIVE0 ft. MGO - General Observation - CONN @ MH 3 AND 9 O' CLOCK/ACTIVE0.9 ft. MGO - General Observation - ROACHES @ MH1.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Finish1.3 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish1.3 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Finish56.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"60 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"109.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"112.1 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: YES, 4", 6" - OPEN161.8 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"164.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"209.7 ft. TFC - Tap Factory Made Capped, at 09 o'clock, -, within 8 inches of joint: NO, 6"212.8 ft. TFC - Tap Factory Made Capped, at 03 o'clock, -, within 8 inches of joint: NO, 6"261.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"264.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"310.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"313.8 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"363.1 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"366.3 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"414.2 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"417.9 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"445.9 ft. SSS - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start445.9 ft. MGO - General Observation - 60% MAG COAT445.9 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start445.9 ft. SAP - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start447.9 ft. MWL - Water Level, 50 %of cross sectional area447.9 ft. AMH - Downstream Manhole, Survey Begins - 14 0159447.9 ft. MWM - Water Mark, 55 %of cross sectional area

Observation photos (4)

  • Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Spalling, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock,  , within 8 inches of joint: YES, Start

    2 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 03 to 09 o'clock, , within 8 inches of joint: YES, Start

  • Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

    2 ft. - Surface Aggregate Projecting, from 09 to 03 o'clock, within 8 inches of joint: YES, Start

  • General Observation - CONN @ MH 3 AND 9 O' CLOCK/ACTIVE

    447.9 ft. - General Observation - CONN @ MH 3 AND 9 O' CLOCK/ACTIVE

Observations (30)

DistanceCodeObservation
447.9AMH14 0160
0MWL
283.4TFC
0AMH14 0159
33.7TFC
30TFA
137.2TFC
186.1TFC
238.2TFC
2SSS
446.6DAGS
0MWM
2MGO60% MAG COAT
2DAGS
335.8TFOPEN
84.8TFC
447MGOROACHES @ MH
183.3TFC
235.1TFC
447.9MGOCONN @ MH 12 AND 1 O'CLOCK/ACTIVE
134.1TFA
446.6SSS
338.7TFC
387.9TFC
446.6SAP
2SAP
286.1TFC
81.6TFC
447.9MGOCONN @ MH 3 AND 9 O' CLOCK/ACTIVE
391.1TFC

Properties (7)

additional_info
630069082521201
custom_field_three
SPALLING/PROJECTING AGGREGATE
custom_field_two
2
customer
1
datetime
2021-08-26T03:27:59-07:00
documentation
PRO PIPE
is_lateral_inspection
false