Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 24, 2021, 04:28 AM
  • 02 1859_02 1858_09232021_213834.mp4

Date
09/23/2021
W/O
911343
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00255
PipeID
P04218
Time
9:28 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9421
Sewer Name
02 DOWNEY-BELLFLOWER RELIEF TRUNK, SECTION 2
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
22
Purpose
Routine Assessment
Project
RFIR_WO_911343_TV02394_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
10 in.
Upstream MH
02 1859
Downstream MH
02 1858
Dir. of Survey
Downstream
Length Surveyed
81 ft.
Total Length
81 ft.
Structural Index
3
Structural Quick
3222
Structural Rating
10
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
10
Pipe schematic from manhole 02 1859 to 02 1858
MH: 02 1859MH: 02 1858downstream0 ft. MWL - Water Level, 15 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 02 18590 ft. MWM - Water Mark, 20 %of cross sectional area11.3 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES36.7 ft. FC - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES67.8 ft. FS - Fracture Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES73.3 ft. FC - Fracture Circumferential, from 10 to 03 o'clock, within 8 inches of joint: YES81 ft. AMH - Downstream Manhole, Survey Ends - 02 1858

Observation photos (4)

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    11.3 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

    36.7 ft. - Fracture Circumferential, from 07 to 10 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES

    67.8 ft. - Fracture Spiral, from 07 to 08 o'clock, within 8 inches of joint: YES

  • Fracture Circumferential, from 10 to 03 o'clock, within 8 inches of joint: YES

    73.3 ft. - Fracture Circumferential, from 10 to 03 o'clock, within 8 inches of joint: YES

Observations (8)

DistanceCodeObservation
67.8FS
36.7FC
81AMH02 1858
11.3CM
73.3FC
0MWL
0AMH02 1859
0MWM

Properties (7)

additional_info
630074092321201
custom_field_three
FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-09-23T21:28:48-07:00
documentation
PROPIPE
is_lateral_inspection
false