Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 24, 2021, 04:54 AM
  • 02 1855_02 1854_09232021_221217.mp4

Date
09/23/2021
W/O
911343
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00255
PipeID
P04214
Time
9:54 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9421
Sewer Name
02 DOWNEY-BELLFLOWER RELIEF TRUNK, SECTION 2
City
PICO RIVERA
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 02
Page No.
25
Purpose
Routine Assessment
Project
RFIR_WO_911343_TV02394_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
18 in.
Width
10 in.
Upstream MH
02 1855
Downstream MH
02 1854
Dir. of Survey
Downstream
Length Surveyed
394.3 ft.
Total Length
394.3 ft.
Structural Index
4
Structural Quick
4B35
Structural Rating
85
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
85
Pipe schematic from manhole 02 1855 to 02 1854
MH: 02 1855MH: 02 1854downstream0 ft. AMH - Upstream Manhole, Survey Begins - 02 18550 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. MWL - Water Level, 15 %of cross sectional area48.3 ft. CL - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES132.4 ft. FS - Fracture Spiral, from 06 to 09 o'clock, within 8 inches of joint: YES187 ft. FL - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES204.9 ft. FM - Fracture Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES211.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES222.9 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES241.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES247.5 ft. FS - Fracture Spiral, from 12 to 03 o'clock, within 8 inches of joint: YES253.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES308 ft. CM - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES329 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES335.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start394.3 ft. AMH - Downstream Manhole, Survey Ends - 02 1854394.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (12)

  • Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

    48.3 ft. - Crack Longitudinal, at 09 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 06 to 09 o'clock, within 8 inches of joint: YES

    132.4 ft. - Fracture Spiral, from 06 to 09 o'clock, within 8 inches of joint: YES

  • Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    187 ft. - Fracture Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES

    204.9 ft. - Fracture Multiple, from 11 to 05 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    211.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    222.9 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    241.5 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 12 to 03 o'clock, within 8 inches of joint: YES

    247.5 ft. - Fracture Spiral, from 12 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    253.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    308 ft. - Crack Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    329 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    335.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (17)

DistanceCodeObservation
247.5FS
204.9FM
308CM
211.2CM
48.3CL
335.3FM
394.3AMH02 1854
132.4FS
394.3FM
0AMH02 1855
241.5FM
0MWM
329FM
222.9FM
187FL
0MWL
253.6FM

Properties (7)

additional_info
630074092321201
custom_field_three
MULTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-09-23T21:54:10-07:00
documentation
PROPIPE
is_lateral_inspection
false