Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 15, 2021, 07:08 AM
  • 16 0079_16 0078_09152021_002309.mp4

Date
09/15/2021
W/O
911589
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00639
PipeID
P13093
Time
12:08 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9408
Sewer Name
16 ALLEN AVENUE TRUNK, SECTS 1,2,&4
City
SAN MARNIO
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 16
Page No.
18
Purpose
Routine Assessment
Project
RFIR_WO_911589_TV16084_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
16 in.
Width
16 in.
Upstream MH
16 0079
Downstream MH
16 0078
Dir. of Survey
Downstream
Length Surveyed
230.2 ft.
Total Length
230.2 ft.
Structural Index
4
Structural Quick
4E3C
Structural Rating
166
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
166
Pipe schematic from manhole 16 0079 to 16 0078
MH: 16 0079MH: 16 0078downstream0 ft. AMH - Upstream Manhole, Survey Begins - 16 00790 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. MWM - Water Mark, 25 %of cross sectional area0 ft. MWL - Water Level, 20 %of cross sectional area6.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start38 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"40.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"86.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"88.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES88.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"94.8 ft. FM - Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES, Start94.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish137.5 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"139.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"186.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: NO, 6"188.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"230 ft. MGO - General Observation - SHELVES AT MH.16.0078 BROKEN230.2 ft. AMH - Downstream Manhole, Survey Ends - 16 0078230.2 ft. FM - Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES, Finish

Observation photos (3)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.6 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    88.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES, Start

    94.8 ft. - Fracture Multiple, from 08 to 05 o'clock, within 8 inches of joint: YES, Start

Observations (19)

DistanceCodeObservation
88.6FM
40.1TFC
230MGOSHELVES AT MH.16.0078 BROKEN
137.5TF
0AMH16 0079
38TF
94.8FM
6.6CM
0MGOCONNECTION AT THE MH 9 OC'LOCK
139.6TF
86.7TFC
188.5TFC
94.8CM
230.2AMH16 0078
186.8TFC
88.6TFC
230.2FM
0MWM
0MWL

Properties (7)

additional_info
630074091421202
custom_field_three
MUTIPLE FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-09-15T00:08:55-07:00
documentation
PROPIPE
is_lateral_inspection
false