Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 26, 2021, 05:53 AM
  • 05 0406_05 0405_08252021_230627.mp4

Date
08/25/2021
W/O
911333
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00465
PipeID
P05618
Time
10:53 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9336
Sewer Name
05 IRWIN AVENUE TRUNK
City
LENNOX
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
09
Purpose
Routine Assessment
Project
WO_911333_TV05051_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
15 in.
Upstream MH
05 0406
Downstream MH
05 0405
Dir. of Survey
Downstream
Length Surveyed
301.8 ft.
Total Length
301.8 ft.
Structural Index
3
Structural Quick
564D
Structural Rating
435
O&M Index
2
O&M Quick
2200
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
439
Pipe schematic from manhole 05 0406 to 05 0405
MH: 05 0406MH: 05 0405downstream0 ft. MWM - Water Mark, 30 %of cross sectional area0 ft. MWL - Water Level, 25 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 04062 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start2 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Start5.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start19.5 ft. FM - Fracture Multiple, from 07 to 01 o'clock, within 8 inches of joint: YES136.9 ft. FS - Fracture Spiral, from 06 to 11 o'clock, within 8 inches of joint: YES140.1 ft. FL - Fracture Longitudinal, at 03 o'clock, within 8 inches of joint: YES140.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES183 ft. B - Broken, from 09 to 05 o'clock, within 8 inches of joint: YES187.6 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES190 ft. FM - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES198.8 ft. B - Broken, from 07 to 12 o'clock, within 8 inches of joint: YES198.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start222 ft. B - Broken, from 07 to 10 o'clock, within 8 inches of joint: YES230.1 ft. FM - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES255 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES260 ft. B - Broken, from 12 to 04 o'clock, within 8 inches of joint: YES265 ft. B - Broken, from 08 to 04 o'clock, within 8 inches of joint: YES299 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish299 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 04 to 08 o'clock, , within 8 inches of joint: YES, Finish299 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish301 ft. MGO - General Observation - ROACHES @ MH301.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish301.8 ft. AMH - Downstream Manhole, Survey Ends - 05 0405

Observation photos (7)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 07 to 01 o'clock, within 8 inches of joint: YES

    19.5 ft. - Fracture Multiple, from 07 to 01 o'clock, within 8 inches of joint: YES

  • Fracture Spiral, from 06 to 11 o'clock, within 8 inches of joint: YES

    136.9 ft. - Fracture Spiral, from 06 to 11 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    140.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

    187.6 ft. - Fracture Multiple, from 09 to 03 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    190 ft. - Fracture Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    198.8 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (26)

DistanceCodeObservation
198.8B
198.8FM
140.1FL
2SSS
255B
299SSS
183B
19.5FM
301.8FM
222B
136.9FS
0MWM
260B
187.6FM
301MGOROACHES @ MH
2DAGS
230.1FM
5.2CM
0MWL
265B
301.8AMH05 0405
299DAGS
190FM
299CM
0AMH05 0406
140.9FM

Properties (7)

additional_info
630074082521201
custom_field_three
MULTIPLE FRACTURE'S/BROKEN PIPE
custom_field_two
2
customer
1
datetime
2021-08-25T22:53:21-07:00
documentation
PROPIPE
is_lateral_inspection
false