Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Aug 26, 2021, 07:21 AM
  • 05 0404_05 0403_08262021_003513.mp4

Date
08/26/2021
W/O
911333
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00465
PipeID
P05616
Time
12:21 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9336
Sewer Name
05 IRWIN AVENUE TRUNK
City
LENNOX
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
09
Purpose
Routine Assessment
Project
WO_911333_TV05051_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
30 in.
Upstream MH
05 0403
Downstream MH
05 0404
Dir. of Survey
Upstream
Length Surveyed
381.3 ft.
Total Length
381.3 ft.
Structural Index
3
Structural Quick
4N3N
Structural Rating
675
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
675
Pipe schematic from manhole 05 0403 to 05 0404
MH: 05 0403MH: 05 0404upstream0 ft. AMH - Upstream Manhole, Survey Ends - 05 04040 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish2.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish376 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start379.3 ft. SSS - Surface Spalling, from 08 to 04 o'clock, within 8 inches of joint: YES, Start379.3 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start381.3 ft. MWM - Water Mark, 20 %of cross sectional area381.3 ft. AMH - Downstream Manhole, Survey Begins - 05 0403381.3 ft. MWL - Water Level, 15 %of cross sectional area

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
379SSS
5.3FM
2SSS
381.3AMH05 0404
0MWM
0AMH05 0403
2CM
0MWL
379CM
381.3FM

Properties (7)

additional_info
630074082521201
custom_field_three
MULTIPLE CRACKS/FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-08-26T00:21:38-07:00
documentation
PROPIPE
is_lateral_inspection
false