Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 2, 2021, 08:07 AM
  • 05 0752_05 0751_09022021_012152.mp4

Date
09/02/2021
W/O
911334
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00521
PipeID
P05977
Time
1:07 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9347
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK, EXTENSION #1
City
INGLEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
07
Purpose
Routine Assessment
Project
WO_911334_TV05308_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
10 in.
Width
10 in.
Upstream MH
05 0752
Downstream MH
05 0751
Dir. of Survey
Downstream
Length Surveyed
344.6 ft.
Total Length
344.6 ft.
Structural Index
3
Structural Quick
413K
Structural Rating
190
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
190
Pipe schematic from manhole 05 0752 to 05 0751
MH: 05 0752MH: 05 0751downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 075234 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start337.9 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES344.6 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish344.6 ft. AMH - Downstream Manhole, Survey Ends - 05 0751

Observation photos (2)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    34 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    337.9 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (7)

DistanceCodeObservation
344.6CM
34CM
344.6AMH05 0751
0MWL
337.9FM
0MWM
0AMH05 0752

Properties (7)

additional_info
630074090121202
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-09-02T01:07:28-07:00
documentation
PROPIPE
is_lateral_inspection
false