Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 1, 2021, 05:01 AM
  • 05 0729_05 0728_08312021_221712.mp4

Date
08/31/2021
W/O
911334
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00521
PipeID
P05952
Time
10:01 PM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9343
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK, EXTENSION #1
City
INGLEWOOD
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
07
Purpose
Routine Assessment
Project
WO_911334_TV05308_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 0729
Downstream MH
05 0728
Dir. of Survey
Downstream
Length Surveyed
324.1 ft.
Total Length
324.1 ft.
Structural Index
4
Structural Quick
4B31
Structural Rating
71
O&M Index
1
O&M Quick
1100
O&M Rating
1
Overall Index
4
Overall Quick
Overall Rating
72
Pipe schematic from manhole 05 0729 to 05 0728
MH: 05 0729MH: 05 0728downstream0 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK0 ft. MGO - General Observation - CONNECTION AT THE MH 9 OC'LOCK0 ft. AMH - Upstream Manhole, Survey Begins - 05 07290 ft. MWL - Water Level, 15 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area3.9 ft. CM - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start35 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"56.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"84.5 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish188.6 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"267.3 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"294.2 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"312.7 ft. TF - Tap Factory Made, at 10 o'clock, -, within 8 inches of joint: NO, 6"318.7 ft. RFJ - Roots Fine Joint, at 08 o'clock, within 8 inches of joint: YES318.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES324.1 ft. AMH - Downstream Manhole, Survey Ends - 05 0728

Observation photos (3)

  • Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

    3.9 ft. - Crack Multiple, from 09 to 04 o'clock, within 8 inches of joint: YES

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    318.7 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

Observations (17)

DistanceCodeObservation
3.9CM
0MGOCONNECTION AT THE MH 3 OC'LOCK
56.3TF
318.7RFJ
7FM
294.2TF
35TF
312.7TF
0MGOCONNECTION AT THE MH 9 OC'LOCK
318.7FM
267.3TF
324.1AMH05 0728
84.5FM
188.6TF
0AMH05 0729
0MWL
0MWM

Properties (7)

additional_info
630074083121201
custom_field_three
FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-08-31T22:01:33-07:00
documentation
PROPIPE
is_lateral_inspection
false