Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 1, 2021, 10:15 AM
  • 05 0722_05 0721_09012021_032829.mp4

Date
09/01/2021
W/O
911334
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00521
PipeID
P05945
Time
3:15 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9343
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK, EXTENSION #1
City
INGLEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
07
Purpose
Routine Assessment
Project
WO_911334_TV05308_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
8 in.
Upstream MH
05 0722
Downstream MH
05 0721
Dir. of Survey
Downstream
Length Surveyed
304.8 ft.
Total Length
304.8 ft.
Structural Index
4
Structural Quick
4K00
Structural Rating
240
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
4
Overall Quick
Overall Rating
240
Pipe schematic from manhole 05 0722 to 05 0721
MH: 05 0722MH: 05 0721downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 07220 ft. MWL - Water Level, 5 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area6.3 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start28.8 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"78.9 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"130.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"181 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"231.7 ft. TF - Tap Factory Made, at 02 o'clock, -, within 8 inches of joint: NO, 6"282.8 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"304.8 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK304.8 ft. AMH - Downstream Manhole, Survey Ends - 05 0721304.8 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    6.3 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (13)

DistanceCodeObservation
0AMH05 0722
78.9TF
304.8MGOCONNECTION AT THE MH 3 OC'LOCK
304.8AMH05 0721
304.8FM
0MWL
231.7TF
6.3FM
181TF
282.8TFC
130.7TF
0MWM
28.8TF

Properties (7)

additional_info
630074083121201
custom_field_three
FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-09-01T03:15:59-07:00
documentation
PROPIPE
is_lateral_inspection
false