Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 1, 2021, 07:12 AM
  • 05 0717_05 0716_09012021_002715.mp4

Date
09/01/2021
W/O
911334
Weather
Dry
Operator/Surveyor
B.FUGATE
Sewer ID
Z00521
PipeID
P05940
Time
12:12 AM
Certificate
U-508-7069
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9343
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK, EXTENSION #1
City
INGLEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
07
Purpose
Routine Assessment
Project
WO_911334_TV05308_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Rectangular
Height
8 in.
Width
10 in.
Upstream MH
05 0717
Downstream MH
05 0716
Dir. of Survey
Downstream
Length Surveyed
316.7 ft.
Total Length
316.7 ft.
Structural Index
4
Structural Quick
4J35
Structural Rating
239
O&M Index
1
O&M Quick
321K
O&M Rating
66
Overall Index
2
Overall Quick
Overall Rating
305
Pipe schematic from manhole 05 0717 to 05 0716
MH: 05 0717MH: 05 0716downstream0 ft. AMH - Upstream Manhole, Survey Begins - 05 07170 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 25 %of cross sectional area11.8 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start17.8 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start36.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish36.4 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start173.5 ft. TFA - Tap Factory Made Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"173.5 ft. RMC - Roots Medium Connection, at 02 o'clock, 25 %, within 8 inches of joint: NO174.8 ft. RMJ - Roots Medium Joint, from 07 to 10 o'clock, 25 %, within 8 inches of joint: YESR316.7 ft. AMH - Downstream Manhole, Survey Ends - 05 0716316.7 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish316.7 ft. RFJ - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish316.7 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK CAPPED

Observation photos (4)

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    11.8 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    17.8 ft. - Roots Fine Joint, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    36.4 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • Roots Medium Joint, from 07 to 10 o'clock, 25 %, within 8 inches of joint: YESR

    174.8 ft. - Roots Medium Joint, from 07 to 10 o'clock, 25 %, within 8 inches of joint: YESR

Observations (14)

DistanceCodeObservation
316.7AMH05 0716
17.8RFJ
316.7FM
316.7RFJ
0AMH05 0717
36.4FM
174.8RMJ
173.5TFA
0MWL
0MWM
173.5RMC
11.8CM
316.7MGOCONNECTION AT THE MH 3 OC'LOCK CAPPED
36.2CM

Properties (7)

additional_info
630074083121201
custom_field_three
FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-09-01T00:12:43-07:00
documentation
PROPIPE
is_lateral_inspection
false