Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 10, 2021, 06:45 AM
  • 05 0714_05 0713_09102021_000443.mp4

Date
09/09/2021
W/O
911334
Weather
Dry
Operator/Surveyor
M.MARTINEZ
Sewer ID
Z00521
PipeID
P05937
Time
11:45 PM
Certificate
U-115-06022794
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9126
Sewer Name
05 SOUTH INGLEWOOD-ORANGE AVENUE TRUNK, EXTENSION #1
City
INGLEWOOD
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 05
Page No.
07
Purpose
Routine Assessment
Project
WO_911334_TV05308_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
10 in.
Upstream MH
05 0714
Downstream MH
05 0713
Dir. of Survey
Downstream
Length Surveyed
361.5 ft.
Total Length
361.5 ft.
Structural Index
3
Structural Quick
3L21
Structural Rating
200
O&M Index
4
O&M Quick
4100
O&M Rating
4
Overall Index
3
Overall Quick
Overall Rating
204
Pipe schematic from manhole 05 0714 to 05 0713
MH: 05 0714MH: 05 0713downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 50 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 05 071417.4 ft. CL - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES29.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES35.2 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start359.7 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish361.5 ft. AMH - Downstream Manhole, Survey Ends - 05 0713361.5 ft. MGO - General Observation - CONNECTION AT THE MH 2 OC'LOCK361.5 ft. MGO - General Observation - CONNECTION AT THE MH 3 OC'LOCK

Observation photos (3)

  • Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

    17.4 ft. - Crack Longitudinal, at 11 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

    29.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    35.2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

Observations (10)

DistanceCodeObservation
361.5AMH05 0713
0MWL
0MWM
35.2CM
361.5MGOCONNECTION AT THE MH 2 OC'LOCK
359.7CM
0AMH05 0714
17.4CL
361.5MGOCONNECTION AT THE MH 3 OC'LOCK
29.4CM

Properties (7)

additional_info
6300740921202
custom_field_three
FRACTURE'S
custom_field_two
2
customer
1
datetime
2021-09-09T23:45:01-07:00
documentation
PROPIPE
is_lateral_inspection
false