Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 24, 2021, 05:47 AM
  • 08 0300A_08 0300_09232021_230230.mp4

Date
09/23/2021
W/O
911332
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00012
PipeID
P00346
Time
10:47 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9377
Sewer Name
08 JAMES STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
07
Purpose
Routine Assessment
Project
WO_911332_TV08023_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
12 in.
Upstream MH
08 0300A
Downstream MH
08 0300
Dir. of Survey
Downstream
Length Surveyed
281.9 ft.
Total Length
281.9 ft.
Structural Index
3
Structural Quick
3J00
Structural Rating
165
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
3
Overall Quick
Overall Rating
165
Pipe schematic from manhole 08 0300A to 08 0300
MH: 08 0300AMH: 08 0300downstream0 ft. MWM - Water Mark, 10 %of cross sectional area0 ft. MGO - General Observation - COCKROACHES IN MANHOLE0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 08 0300A0 ft. MWL - Water Level, 5 %of cross sectional area5.4 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start21 ft. MGO - General Observation - PIPE'S (VCP) SURFACE IS ROUGH THROUGHOUT LINE.57 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"77.7 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"78.8 ft. TBA - Tap Break-In Active, at 02 o'clock, -, within 8 inches of joint: NO, 6"152.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"257.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"279.5 ft. CM - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Finish281.9 ft. MGO - General Observation - COCKROACHES IN MANHOLE281.9 ft. AMH - Downstream Manhole, Survey Ends - 08 0300

Observation photos (3)

  • General Observation - COCKROACHES IN MANHOLE

    0 ft. - General Observation - COCKROACHES IN MANHOLE

  • Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

    5.4 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

  • General Observation - COCKROACHES IN MANHOLE

    281.9 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (15)

DistanceCodeObservation
281.9MGOCOCKROACHES IN MANHOLE
21MGOPIPE'S (VCP) SURFACE IS ROUGH THROUGHOUT LINE.
0MWM
279.5CM
57TFC
281.9AMH08 0300
77.7TBA
0MGOCOCKROACHES IN MANHOLE
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
0AMH08 0300A
152.6TFC
257.6TFC
78.8TBA
0MWL
5.4CM

Properties (7)

additional_info
630069092321201
custom_field_three
CRACKS
custom_field_two
2
customer
1
datetime
2021-09-23T22:47:53-07:00
documentation
PRO PIPE
is_lateral_inspection
false