Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Sep 24, 2021, 06:36 AM
  • 08 0299_08 0298_09232021_234329.mp4

Date
09/23/2021
W/O
911332
Weather
Dry
Operator/Surveyor
S. LOPEZ
Sewer ID
Z00012
PipeID
P00344
Time
11:36 PM
Certificate
U-0720-70309212
System Owner
1
Date Cleaned
Pre-Cleaning
No Pre-Cleaning
Media Label
K9377
Sewer Name
08 JAMES STREET TRUNK
City
GARDENA
Loc. details
Main Highway - Urban
Location Code
A
Use of Sewer
Sanitary Sewer
District
District 08
Page No.
07
Purpose
Routine Assessment
Project
WO_911332_TV08023_SEP2021
Sewer Type
Gravity
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Width
12 in.
Upstream MH
08 0299
Downstream MH
08 0298
Dir. of Survey
Downstream
Length Surveyed
79.6 ft.
Total Length
79.6 ft.
Structural Index
3
Structural Quick
3100
Structural Rating
3
O&M Index
2
O&M Quick
2B00
O&M Rating
30
Overall Index
2
Overall Quick
Overall Rating
33
Pipe schematic from manhole 08 0299 to 08 0298
MH: 08 0299MH: 08 0298downstream0 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 9 O'CLOCK0 ft. AMH - Upstream Manhole, Survey Begins - 08 02990 ft. MWL - Water Level, 5 %of cross sectional area2 ft. MWM - Water Mark, 5 %of cross sectional area2.5 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start13.1 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: NO, 6"44.1 ft. CM - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES77.3 ft. DAGS - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Finish79.6 ft. MGO - General Observation - COCKROACHES IN MANHOLE79.6 ft. MGO - General Observation - ACTIVE CONNECTION AT MH 3 O'CLOCK79.6 ft. AMH - Downstream Manhole, Survey Ends - 08 0298

Observation photos (3)

  • Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock,  , within 8 inches of joint: YES, Start

    2.5 ft. - Deposits Attached Grease, 5 %of cross sectional area, from 02 to 10 o'clock, , within 8 inches of joint: YES, Start

  • Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

    44.1 ft. - Crack Multiple, from 10 to 02 o'clock, within 8 inches of joint: YES

  • General Observation - COCKROACHES IN MANHOLE

    79.6 ft. - General Observation - COCKROACHES IN MANHOLE

Observations (11)

DistanceCodeObservation
44.1CM
79.6MGOCOCKROACHES IN MANHOLE
2.5DAGS
2MWM
77.3DAGS
13.1TFC
0MGOACTIVE CONNECTION AT MH 9 O'CLOCK
79.6MGOACTIVE CONNECTION AT MH 3 O'CLOCK
0AMH08 0299
79.6AMH08 0298
0MWL

Properties (7)

additional_info
630069092321201
custom_field_three
CRACKS
custom_field_two
3
customer
1
datetime
2021-09-23T23:36:44-07:00
documentation
PRO PIPE
is_lateral_inspection
false