Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 14, 2021, 11:28 AM
  • 15 0394_15 0393_10142021_042956.mp4

Date
10/14/2021
W/O
091798
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00597
PipeID
P12317
Time
4:28 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1974
Sewer Name
15 ARROYO DRIVE TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
31
Purpose
Routine Assessment
Project
20211013MDM_ARROYO_DRIVE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
15 0394
Downstream MH
15 0393
Dir. of Survey
Downstream
Length Surveyed
116.5 ft.
Total Length
116.5 ft.
Structural Index
2
Structural Quick
2A00
Structural Rating
24
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
24
Pipe schematic from manhole 15 0394 to 15 0393
MH: 15 0394MH: 15 0393downstream0 ft. AMH - Upstream Manhole, Survey Begins - 4:30AM0 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area8.3 ft. FC - Fracture Circumferential, from 10 to 03 o'clock, within 8 inches of joint: YES - SLIGHT13 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped14.4 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL17.7 ft. FC - Fracture Circumferential, from 10 to 02 o'clock, within 8 inches of joint: YES - SL38 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - SL41.5 ft. FC - Fracture Circumferential, from 11 to 01 o'clock, within 8 inches of joint: YES - H45.5 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped47.2 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL57.3 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL57.3 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - SL60.7 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL61.7 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped83.6 ft. FC - Fracture Circumferential, from 09 to 04 o'clock, within 8 inches of joint: YES - H94.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped110.1 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL110.8 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped112.6 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL116.5 ft. AMH - Downstream Manhole, Survey Ends - 4:45AM

Observation photos (1)

  • Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL

    60.7 ft. - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL

Observations (22)

DistanceCodeObservation
47.2FCSL
61.7TFCCapped
57.3FCSL
8.3FCSLIGHT
94.6TFCCapped
57.3FCSL
110.8TFCCapped
112.6FCSL
0AMH4:30AM
116.5AMH4:45AM
13TFCCapped
38FCSL
0MGOConn. @ Mh, 3 O' Clock. Active
0MWL
17.7FCSL
14.4FCSL
45.5TFCCapped
0MWM
60.7FCSL
110.1FCSL
83.6FCH
41.5FCH

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2021-10-14T04:28:25-07:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false