Sanitation Districts of Los Angeles Countyt4 Spatial
Wastewater/Activity/PacpInspection/1.0Oct 14, 2021, 11:06 AM
  • 15 0395_15 0394_10142021_041518.mp4

Date
10/14/2021
W/O
091798
Weather
Dry
Operator/Surveyor
MARTIN
Sewer ID
Z00597
PipeID
P12318
Time
4:06 AM
Certificate
U-1014-06022543
System Owner
LACSD
Date Cleaned
Pre-Cleaning
Not Known
Media Label
H1974
Sewer Name
15 ARROYO DRIVE TRUNK
City
MONTEBELLO
Loc. details
Light Highway
Location Code
C
Use of Sewer
Sanitary Sewer
District
District 15
Page No.
31
Purpose
Routine Assessment
Project
20211013MDM_ARROYO_DRIVE_TRUNK
Material
Vitrified Clay Pipe
Shape
Circular
Height
8 in.
Upstream MH
15 0395
Downstream MH
15 0394
Dir. of Survey
Downstream
Length Surveyed
98.8 ft.
Total Length
98.8 ft.
Structural Index
2
Structural Quick
4132
Structural Rating
30
O&M Index
0
O&M Quick
0000
O&M Rating
0
Overall Index
2
Overall Quick
Overall Rating
30
Pipe schematic from manhole 15 0395 to 15 0394
MH: 15 0395MH: 15 0394downstream0 ft. MWL - Water Level, 10 %of cross sectional area0 ft. MWM - Water Mark, 20 %of cross sectional area0 ft. AMH - Upstream Manhole, Survey Begins - 4:15AM8 ft. FC - Fracture Circumferential, from 08 to 10 o'clock, within 8 inches of joint: YES - HAIRLINE9 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped11.3 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SLIGHT11.3 ft. FC - Fracture Circumferential, from 09 to 12 o'clock, within 8 inches of joint: YES - H14.4 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - H14.4 ft. FC - Fracture Circumferential, from 03 to 04 o'clock, within 8 inches of joint: YES - SL17.9 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - H17.9 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - H41.6 ft. FL - Fracture Longitudinal, at 10 o'clock, within 8 inches of joint: YES - SL45 ft. FC - Fracture Circumferential, from 12 to 04 o'clock, within 8 inches of joint: YES - SL45.6 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped47.6 ft. FC - Fracture Circumferential, from 08 to 11 o'clock, within 8 inches of joint: YES - SL47.6 ft. FC - Fracture Circumferential, from 01 to 04 o'clock, within 8 inches of joint: YES - H57.6 ft. FM - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL58.3 ft. TFC - Tap Factory Made Capped, at 10 o'clock, -, within 8 inches of joint: YES, 6" - Capped83.8 ft. FC - Fracture Circumferential, from 02 to 04 o'clock, within 8 inches of joint: YES - SL94.7 ft. TFC - Tap Factory Made Capped, at 02 o'clock, -, within 8 inches of joint: YES, 6" - Capped98.4 ft. MGO - General Observation - Conn. @ Mh, 3 O' Clock. Active98.8 ft. AMH - Downstream Manhole, Survey Ends - 4:25AM

Observation photos (1)

  • Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

    57.6 ft. - Fracture Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES - SL

Observations (22)

DistanceCodeObservation
98.8AMH4:25AM
0MWL
11.3FCSLIGHT
17.9FCH
14.4FLH
83.8FCSL
0MWM
47.6FCSL
9TFCCapped
98.4MGOConn. @ Mh, 3 O' Clock. Active
0AMH4:15AM
11.3FCH
58.3TFCCapped
45.6TFCCapped
45FCSL
8FCHAIRLINE
94.7TFCCapped
57.6FMSL
47.6FCH
14.4FCSL
17.9FCH
41.6FLSL

Properties (6)

custom_field_three
SLIGHT FRACTURES
custom_field_two
3
customer
LACSD
datetime
2021-10-14T04:06:34-07:00
documentation
MARTIN,REVELES,OLIVER 111,CASTILLO
is_lateral_inspection
false