- Date
- 09/15/2021
- W/O
- 911340
- Weather
- Dry
- Operator/Surveyor
- B.FUGATE
- Sewer ID
- Z00639
- PipeID
- P13107
- Time
- 2:26 AM
- Certificate
- U-508-7069
- System Owner
- 1
- Date Cleaned
- —
- Pre-Cleaning
- No Pre-Cleaning
- Media Label
- K9407
- Sewer Name
- 16 ALLEN AVENUE TRUNK, SECTS 1,2,&4
- City
- SAN MARINO
- Loc. details
- Main Highway - Urban
- Location Code
- A
- Use of Sewer
- Sanitary Sewer
- District
- District 16
- Page No.
- 14
- Purpose
- Routine Assessment
- Project
- RFIR_WO_911340_TV16121_SEP2021
- Sewer Type
- Gravity
- Material
- Vitrified Clay Pipe
- Shape
- Circular
- Height
- 18 in.
- Width
- 18 in.
- Upstream MH
- 16 0092
- Downstream MH
- 16 0093
- Dir. of Survey
- Upstream
- Length Surveyed
- 345.5 ft.
- Total Length
- 345.5 ft.
- Structural Index
- 3
- Structural Quick
- 413M
- Structural Rating
- 347
- O&M Index
- 2
- O&M Quick
- 2Z00
- O&M Rating
- 274
- Overall Index
- 2
- Overall Quick
- —
- Overall Rating
- 621
Pipe schematic from manhole 16 0092 to 16 0093 Observation photos (3)

2 ft. - Crack Multiple, from 08 to 04 o'clock, within 8 inches of joint: YES, Start

2.1 ft. - Deposits Settled Other, 10 %of cross sectional area, from 05 to 07 o'clock, , within 8 inches of joint: YES, Start

23.5 ft. - Fracture Multiple, from 01 to 05 o'clock, within 8 inches of joint: YES